86
Computing the Cycle Time
Section 2-7
Here,
2-7-10 Pulse Output Start Time
The pulse output start time is the time required from executing a pulse output
instruction until pulses are output externally. This time depends on the pulse
output instruction that is used and operation that is performed.
2-7-11 Pulse Output Change Response Time
The pulse output change response time is the time for any change made by
executing an instruction during pulse output to actually affect the pulse output
operation.
Number of partici-
pating slave nodes
The number of slaves to which links have been established
within the maximum unit number set in the master.
Number of non-par-
ticipating slave
nodes
The number of slaves not participating in the links within the
maximum unit number set in the master
Communications
cycle time (ms)
Slave communications time
×
Number of participating slave
nodes + 10
×
Number of non-participating slave nodes
Slave communica-
tions time (ms)
• Communications time set to
Standard
0.4 + 0.286
×
((No. of 1)
×
No. of link words
×
2 + 12)
• Communications time set to
Fast
0.4 + 0.0955
×
((No. of 1)
×
No. of link words
×
2 +
12)
Pulse output instruction
Start time
SPED: continuous
86
µ
s
SPED: independent
98
µ
s
ACC: continuous
103
µ
s
ACC: independent, trapezoidal
122
µ
s
ACC: independent, triangular
123
µ
s
PLS2: trapezoidal
145
µ
s
PLS2: triangular
146
µ
s
Start time
Instruction execution
Pulse output
Pulse output instruction
Change response time
INI: immediate stop
63
µ
s + 1 pulse output time
SPED: immediate stop
106
µ
s + 1 pulse output time
ACC: deceleration stop
1 control cycle (4 ms) minimum,
2 control cycles (8 ms) maximum
PLS2: deceleration stop
SPED: speed change
ACC: speed change
PLS2: target position change in
reverse direction
PLS2: target position change in
same direction at same speed
PLS2: target position change in
same direction at different speed
Содержание CP1L - 12-2007
Страница 3: ...iv...
Страница 9: ...x...
Страница 13: ...xiv TABLE OF CONTENTS...
Страница 21: ...xxii...
Страница 33: ...xxxiv Conformance to EC Directives 6...
Страница 65: ...32 Function Blocks Section 1 5...
Страница 428: ...395 Clock Section 6 9...
Страница 429: ...396 Clock Section 6 9...
Страница 523: ...488 Troubleshooting Unit Errors Section 9 4...
Страница 531: ...496 Replacing User serviceable Parts Section 10 2...
Страница 563: ...528 Auxiliary Area Allocations by Function Appendix C...
Страница 611: ...576 Auxiliary Area Allocations by Address Appendix D...
Страница 638: ...603 Connections to Serial Communications Option Boards Appendix F Connecting to Unit...
Страница 639: ...604 Connections to Serial Communications Option Boards Appendix F...
Страница 669: ...634 Index...
Страница 671: ...636 Revision History...