601
Connections to Serial Communications Option Boards
Appendix F
Wiring Connectors
Use the following steps to wire connectors.
See the following diagrams for the length of the cable portion to be cut in each step.
Shield Connected to Hood (FG)
1.
Cut the cable to the required length.
2.
Remove the specified length of the sheath from the cable using a knife. Be careful not to scratch the braided
shield.
3.
Trim off the braided shield using scissors so that the remaining shield length is 10 mm.
4.
Remove the insulation from each conductor using a stripper so that the exposed conductor length is 5 mm.
5.
Fold back the braided shield.
6.
Wrap aluminum foil tape around the folded shield.
Shield Not Connected to Hood (FG)
1.
Cut the cable to the required length.
2.
Remove the specified length of the sheath from the cable using a knife. Be careful not to scratch the braided
shield.
3.
Trim off all the braided shield using scissors.
4.
Remove the insulation from each conductor using a stripper so that the exposed conductor length is 5 mm.
25 mm (RS-422A)
40 mm (RS-232C)
10 mm
5 mm
Aluminum foil tape
25 mm (RS-422A)
40 mm (RS-232C)
5 mm
Содержание CP1L - 12-2007
Страница 3: ...iv...
Страница 9: ...x...
Страница 13: ...xiv TABLE OF CONTENTS...
Страница 21: ...xxii...
Страница 33: ...xxxiv Conformance to EC Directives 6...
Страница 65: ...32 Function Blocks Section 1 5...
Страница 428: ...395 Clock Section 6 9...
Страница 429: ...396 Clock Section 6 9...
Страница 523: ...488 Troubleshooting Unit Errors Section 9 4...
Страница 531: ...496 Replacing User serviceable Parts Section 10 2...
Страница 563: ...528 Auxiliary Area Allocations by Function Appendix C...
Страница 611: ...576 Auxiliary Area Allocations by Address Appendix D...
Страница 638: ...603 Connections to Serial Communications Option Boards Appendix F Connecting to Unit...
Страница 639: ...604 Connections to Serial Communications Option Boards Appendix F...
Страница 669: ...634 Index...
Страница 671: ...636 Revision History...