OMNI 4000/7000 Operations and Maintenance Guide
– Rev F
5-5
OMNICONNECT® Data Retrieval
3.
Update the fields, as applicable.
There are two ways to access the
Database Browser
for the
Boolean
Trigger
:
a. Click the
ellipses
button, or
b. Right-click in the
Boolean Trigger
field.
4.
Click
Apply
to save your changes.
5.3.2 Run Archives
At the bottom of the
Archive
screen is the
Archive Status
. The default status for all
archives is
STOPPED,
and the ability to configure them is
ENABLED
. To start the
archiving feature and begin collecting the data, the configuration status must first be
disabled.
To run the archives and collect the raw data, follow these instructions:
1.
In the Actions ribbon, click
Operate
.
The only way to view the
Database Browser
and make
your selection for point numbers is
to right-click in the activated field.
If the entire row is selected, you
will not get the browser option.