OMNI 4000/7000 Operations and Maintenance Guide
– Rev F
7-9
Maintenance
3.
Select an analog input calibration to verify
by following the instructions in Steps 3
through 8 in the Analog Inputs section in
Section 7.2.2 Calibration.
After you apply your chosen
Calibration
Units
, the
Verify Input
group will appear.
4.
a. Enter the
Applied Value
from the
calibration verification
instrumentation.
b. Click
Verify Input
.
5.
The
Error
field will now display the
percentage of error of the verification.
a. If the percentage of error is within
acceptable limits, you do not need to
re-calibrate the input channel.
b. If the percentage of error is not within
acceptable limits, you may need to
re-calibrate the input channel (go to
Section 7.2.2).
c. Click
End Verification
to stop the
process.
Analog Output Verification
To verify that the output calibration variables are correct or within the acceptable error tolerance,
follow these instructions:
1.
In the Actions ribbon, click
Diagnostics
.
2.
Click on
Calibration Verification
in the
Diagnostics
tree.