OMNI 4000/7000 Operations and Maintenance Guide
– Rev F
6-18
Front Panel Operations
4.
You can edit some of the variables for any
of the batches currently configured, such
as
Batch ID Number
,
Adjust Batch Size
,
Batch Remaining
and any of the
Batch
Total
values.
a. Use the arrow keys to select the
variable you wish to edit.
b. Press
OK
to access the field and
make changes.
c. Press
OK
or the
Accept
function key
to save your changes.
5.
Use the
Right
or
Left
arrow keys to select
a different Meter Run or Station (at the top
of the screen) to view or edit its batch
operations.
If a Station is running a common batch stack, it will be listed on its
Batch Control
screen (left). The Meter Runs defined as part of a Station and using a common batch
stack will display a notice (right) rather than displaying individual Meter Run batch
details as it would for a Meter using an Independent batch stack.
6.
To end a selected batch and generate a
report, either press the
End+Shift
function
key or the
End
function key.
The
End+Shift
function key ends
the current batch, but it allows the
next batch in the sequence to
start on the next product in the
batch stack queue. The
End
function key ends the current
batch and starts a new batch with
the same product as was running
before, not allowing a batch stack
to shift to the next product in
the queue.