OMNI 4000/7000 Operations and Maintenance Guide
– Rev F
7-28
Maintenance
14.
Press the
Apply Low
function key to
complete the
Low
adjustment or the
Abort
function key to discard.
15.
Adjust the
Signal Generator
or configure
the
Transmitter
, whichever is connected,
to output the appropriate
HI
value
according to the selected calibration units.
16.
Confirm that the
Live Input (mA/Ohms)
field value in the
Apply High Input
Source
screen is close to the applied
value from the field transmitter or
signal generator.
If the value is not close to the applied
value, check:
•
The wiring is connected to the correct
channel.
•
The hardware jumper settings.
17.
Wait 20 to 30 seconds for the readings to
stabilize.
18.
While the
Applied Input Value?
field is
highlighted, press
OK
.
19.
Using the numeric keypad, enter a value
that exactly matches the value at the field
transmitter or the signal generator.
Press
OK
.
High values are 20.00 mA for a
4
‒20 mA input, 5 V for a 1‒5 V
input, and 150 ohms for an
RTD input.