5 6 Ramp & Dwell
5 6 Ramp & Dwell
Example 1: Temperature cycling Chamber
Example 1: Temperature cycling Chamber
EIFN=SP.P2
A1FN=TIMR
OUT1=REVR, Relay Output
OUT2=COOL, 4-20mA Output
SPMD=MINR
IN1U= °C
DP1=1-DP
EIFN=SP.P2
A1FN=TIMR
OUT1=REVR, Relay Output
OUT2=COOL, 4-20mA Output
SPMD=MINR
IN1U= °C
DP1=1-DP
The circuit diagram and its temperature profile are shown below:
The circuit diagram and its temperature profile are shown below:
A chamber is used to test the temperature cycling effect on personal
computers. An external cycle timer is used to control the event input for
switching the set point. The products under test are required to stay at 60 °C
for 1 hour and -10 °C for 30 minutes. The transition interval between high-low
temperature is required to be 5 minutes. Make the following setup:
A chamber is used to test the temperature cycling effect on personal
computers. An external cycle timer is used to control the event input for
switching the set point. The products under test are required to stay at 60 °C
for 1 hour and -10 °C for 30 minutes. The transition interval between high-low
temperature is required to be 5 minutes. Make the following setup:
ETR-8300
Freezer
Heater
Inverter
ON
OFF
65
35
Cycle Timer
Cycle Timer
AC Relay
AC Relay
1
Mains
1
Mains
3
AC
3
AC
+
RTD
Chamber
Figure 5.8
Figure 5.8
A Temperature Cycling Chamber
A Temperature Cycling Chamber
90
TIME=60.0 (minutes )
SP1=60.0 °C
SP2=-10.0 °C
CPB=100 (%)
RAMP=14.0 ( °C/minute )
TIME=60.0 (minutes )
SP1=60.0 °C
SP2=-10.0 °C
CPB=100 (%)
RAMP=14.0 ( °C/minute )