3 16 Failure Transfer
3 16 Failure Transfer
The controller will enter
as one of the following conditions occurs:
1.
occurs ( due to the input 1 sensor break or input 1 current below 1mA
if 4-20 mA is selected or input 1 voltage below 0.25V if 1-5 V is selected ) if
PV1, P1-2 or P2-1 is selected for PVMD or PV1 is selected for SPMD.
2.
occurs ( due to the input 2 sensor break or input 2 current below 1mA
if 4-20 mA is selected or input 2 voltage below 0.25V if 1-5 V is selected ) if
PV2, P1-2 or P2-1 is selected for PVMD or PV2 is selected for SPMD.
3.
occurs due to the A-D converter of the controller fails.
failure mode
SB1E
SB2E
ADER
The controller will enter
as one of the following conditions occurs:
1.
occurs ( due to the input 1 sensor break or input 1 current below 1mA
if 4-20 mA is selected or input 1 voltage below 0.25V if 1-5 V is selected ) if
PV1, P1-2 or P2-1 is selected for PVMD or PV1 is selected for SPMD.
2.
occurs ( due to the input 2 sensor break or input 2 current below 1mA
if 4-20 mA is selected or input 2 voltage below 0.25V if 1-5 V is selected ) if
PV2, P1-2 or P2-1 is selected for PVMD or PV2 is selected for SPMD.
3.
occurs due to the A-D converter of the controller fails.
failure mode
SB1E
SB2E
ADER
The output 1 and output 2 will perform the
function as one of the
following conditions occurs:
1. During power starts ( within 2.5 seconds ).
2. The controller enters the failure mode.
3. The controller enters the manual mode.
4. The controller enters the calibration mode.
failure transfer
The output 1 and output 2 will perform the
function as one of the
following conditions occurs:
1. During power starts ( within 2.5 seconds ).
2. The controller enters the failure mode.
3. The controller enters the manual mode.
4. The controller enters the calibration mode.
failure transfer
Output 1 Failure Transfer, if activated, will perform :
1. If output 1 is configured as proportional control ( PB1 = 0 ), and BPLS is
selected for O1FT, then output 1 will perform bumpless transfer. Thereafter
the previous averaging value of MV1 will be used for controlling output 1.
2. If output 1 is configured as proportional control ( PB1 = 0 ), and a value of
0 to 100.0 % is set for O1FT, then output 1 will perform failure transfer.
Thereafter the value of O1FT will be used for controlling output 1.
3. If output 1 is configured as ON-OFF control ( PB1 = 0 ), then output 1 will be
driven OFF if O1FN selects REVR and be driven ON if O1FN selects DIRT.
Output 1 Failure Transfer, if activated, will perform :
1. If output 1 is configured as proportional control ( PB1 = 0 ), and BPLS is
selected for O1FT, then output 1 will perform bumpless transfer. Thereafter
the previous averaging value of MV1 will be used for controlling output 1.
2. If output 1 is configured as proportional control ( PB1 = 0 ), and a value of
0 to 100.0 % is set for O1FT, then output 1 will perform failure transfer.
Thereafter the value of O1FT will be used for controlling output 1.
3. If output 1 is configured as ON-OFF control ( PB1 = 0 ), then output 1 will be
driven OFF if O1FN selects REVR and be driven ON if O1FN selects DIRT.
Output 2 Failure Transfer
Alarm 1 Failure Transfer
, if activated, will perform :
1. If OUT2 selects COOL, and BPLS is selected for O1FT, then output 2 will
perform bumpless transfer. Thereafter the previous averaging value of MV2
will be used for controlling output 2.
2. If OUT2 selects COOL, and a value of 0 to 100.0 % is set for O2FT, then
output 2 will perform failure transfer. Thereafter the value of O1FT will be
used for controlling output 2.
is activated as the controller enters failure mode.
Thereafter the alarm 1 will transfer to the ON or OFF state preset by A1FT.
Output 2 Failure Transfer
Alarm 1 Failure Transfer
, if activated, will perform :
1. If OUT2 selects COOL, and BPLS is selected for O1FT, then output 2 will
perform bumpless transfer. Thereafter the previous averaging value of MV2
will be used for controlling output 2.
2. If OUT2 selects COOL, and a value of 0 to 100.0 % is set for O2FT, then
output 2 will perform failure transfer. Thereafter the value of O1FT will be
used for controlling output 2.
is activated as the controller enters failure mode.
Thereafter the alarm 1 will transfer to the ON or OFF state preset by A1FT.
Failure Mode Occurs as :
1. SB1E
2. SB2E
3. ADER
Failure Mode Occurs as :
1. SB1E
2. SB2E
3. ADER
Failure Transfer of outout 1 and output 2
occurs as :
1. Power start ( within 2.5 seconds )
2. Failure mode is activated
3. Manual mode is activated
4. Calibration mode is activated
Failure Transfer of outout 1 and output 2
occurs as :
1. Power start ( within 2.5 seconds )
2. Failure mode is activated
3. Manual mode is activated
4. Calibration mode is activated
Failure Transfer of alarm 1 and alarm 2
occurs as :
1. Failure mode is activated
Failure Transfer of alarm 1 and alarm 2
occurs as :
1. Failure mode is activated
Failure Transfer Setup :
1. O1FT
2. O2FT
3. A1FT
4. A2FT
Failure Transfer Setup :
1. O1FT
2. O2FT
3. A1FT
4. A2FT
56
Alarm 2 Failure Transfer is activated as the controller enters failure mode.
Thereafter the alarm 2 will transfer to the ON or OFF state preset by A2FT.
Alarm 2 Failure Transfer is activated as the controller enters failure mode.
Thereafter the alarm 2 will transfer to the ON or OFF state preset by A2FT.
Exception:
If Loop Break (LB) alarm or sensor Break (SENB) alarm is
configured for A1FN, the alarm 1 will be switched to ON state independent
of the setting of A1FT. If Dwell Timer (TIMR) is configured for A1FN, the alarm 1
will not perform failure transfer.
Exception:
If Loop Break (LB) alarm or sensor Break (SENB) alarm is
configured for A1FN, the alarm 1 will be switched to ON state independent
of the setting of A1FT. If Dwell Timer (TIMR) is configured for A1FN, the alarm 1
will not perform failure transfer.
Exception: If Loop Break (LB) alarm or sensor Break (SENB) alarm is
configured for A2FN, the alarm 2 will be switched to ON state independent
of the setting of A2FT. If Dwell Timer (TIMR) is configured for A2FN, the alarm 2
will not perform failure transfer.
Exception: If Loop Break (LB) alarm or sensor Break (SENB) alarm is
configured for A2FN, the alarm 2 will be switched to ON state independent
of the setting of A2FT. If Dwell Timer (TIMR) is configured for A2FN, the alarm 2
will not perform failure transfer.