3 5 Cool Only Control
3 5 Cool Only Control
ON-OFF control, P (PD) control and PID control can be used for cooling
applications. This is accomplished by setting OUT1 to DIRT (direct action).
The other functions for
control,
control
and
control are the same as descriptions in section 3-4 for heat
only control. The only difference is that the output variable (and action) for
the cool control is inverse to the heat control, such as the following diagram
shows:
cool only ON-OFF
cool only P ( PD )
cool only PID
ON-OFF control, P (PD) control and PID control can be used for cooling
applications. This is accomplished by setting OUT1 to DIRT (direct action).
The other functions for
control,
control
and
control are the same as descriptions in section 3-4 for heat
only control. The only difference is that the output variable (and action) for
the cool control is inverse to the heat control, such as the following diagram
shows:
cool only ON-OFF
cool only P ( PD )
cool only PID
SP1+O1HY/2
SP1 O1HY/2
SP1
ON
OFF
OUT1 Action
PV
Dead band = O1HY
Time
Time
Figure 3.3 Cool Only
ON-OFF Control
Figure 3.3 Cool Only
ON-OFF Control
Setup Cool Control :
OUT1 =
Setup Cool Control :
OUT1 =
Refer to section 3-4 in which similar descriptions for heat only control can be
applied to cool only control.
Refer to section 3-4 in which similar descriptions for heat only control can be
applied to cool only control.
44