Troubleshooting
4-13
Part 1603054-02
E
2015 Nordson Corporation
7. Move the SW1 address switches back to their original positions.
8. Turn off the power to the pump cabinet, wait 5 seconds, then turn the
power back on.
9. Remove the plugs from the pattern air output fittings and re-connect the
pattern air tubing.
10. At the iControl console, check each gun control screen that was
previously indicating air flow when the gun was off. No air flow should
be indicated.
Address
Switch
SW1
TEST Button
Dual HDLV Pump Control Board
Obsolete