AB
abort motion
IMM
PGM
MIP
USAGE
♦
♦
SYNTAX
AB
PARAMETERS
None.
DESCRIPTION
This command should be used as an emergency stop. On reception of this
command, the controller invokes emergency stop event processing for each axis
as configured by
ZE
(e-stop event configuration) command.
By default axes are configured to turn motor power OFF, however, individual
axes can be configured to stop using emergency deceleration rate set by
AE
command and maintain motor power.
It should be used only as an immediate command, not in a program.
Note:
This command affects all axes, however the action taken is determined by each
individual’s axis
ZE
command configuration.
RETURNS
none
REL. COMMANDS
ST
-
stop motion
AE
-
e-stop deceleration
ZE
-
e-stop deceleration
MF
-
motor OFF
MO
-
motor ON
EXAMPLE
AB
| used as an immediate command to stop all motion