DE
enable/disable data acquisition
IMM
PGM MIP
USAGE
♦
♦
PARAMETERS nn
Description
nn
[ int ] -
True | False
Range
nn
-
1
for True,
0
for False
DESCRIPTION
This command is used to enable / disable the data acquisition request.
This command cannot be issued when:
1.
An axis is being homed (refer ASCII command,
OR
).
2.
An axis is being moved to a travel limit (refer ASCII command,
MT
).
SYNTAX
DE
nn
Note:
3.
An axis is being moved to an index (refer ASCII command,
MZ
).
RETURNS
None
REL. COMMANDS
DC
-
setup data acquisition request
DG -
get acquired data
DF
-
data acquisition status, returns # of samples collected
DD
-
data acquisition done status
EXAMPLE
DC1,1,0,4,1,500
nn1
=1 : Start data acquisition when trigger axis start motion
nn2
=1 : Trigger axis is 1
nn3
=0
nn4
=4 : Position feedback from channel 3
nn6
=500 : Collect 500 samples
DE1
Enable data acquisition
DD
Query data acquisition done status
If true,
DEO
Disable data acquisition
DF
Get data acquisition sample count
DG
Get data collected
nn5
=1 : Collect data entry often servo cycle
1 = true 0 = false
500
Controller responds with number samples collected
3-46
Section
3
–
Remote
Mode
Содержание ESP300 Series
Страница 1: ...ESP300 Motion Controller Driver User s Manual...
Страница 4: ...ESP300 1999 EU Declaration of Conformity iv Preface...
Страница 29: ...This page is intentionally left blank Section 2 Modes of Operation 1 15...
Страница 30: ......
Страница 230: ...4 16 Section 4 Advanced Capabilities...
Страница 274: ...This page is intentionally left blank 6 6 Section 6 Servo Tuning...
Страница 290: ...This page is intentionally left blank B 6 Appendix B Trouble Shooting and Maintenance...