JH
set jog high speed
IMM PGM MIP
USAGE
♦
♦
♦
Range
xx
-
1
to
MAX AXES
REL. COMMANDS
JW
-
set jog low speed
SYNTAX
xx
JH
nn or xx
JH
?
PARAMETERS
Description
xx
[ int ]
-
axis number
nn
[ float ] -
high speed value
nn
-
0
to
maximum value allowed by VU command
or
?
to read present setting
Units
xx
-
none
nn
-
preset
units/second
Defaults xx
missing:
error 37, AXIS NUMBER MISSING
out of range:
error 9, AXIS NUMBER OUT OF RANGE
nn
missing:
error 38, COMMAND PARAMETER MISSING
out of range:
error xx10, MAXIMUM VELOCITY EXCEEDED
DESCRIPTION
This command is used to set the high speed for jogging an axis. Its execution is
immediate, meaning that the value is changed when the command is processed,
including when motion is in progress. It can be used as an immediate command
or inside a program.
RETURNS
If “?” sign takes the place of
nn
value, this command reports current setting.
VU
-
set maximum velocity
EXAMPLE
2VU?
|
read maximum velocity allowed axis # 2
10
|
controller returns a
value of 10.0 units/second for axis #2
2JH7.5
|
set jog high speed to 7.5 units/second for axis #2
2JH?
|
read jog high speed value for axis #2
7.5
| controller returns a value of 7.5 units/second for axis #2
Section 3 – Remote Mode
3-87
Содержание ESP300 Series
Страница 1: ...ESP300 Motion Controller Driver User s Manual...
Страница 4: ...ESP300 1999 EU Declaration of Conformity iv Preface...
Страница 29: ...This page is intentionally left blank Section 2 Modes of Operation 1 15...
Страница 30: ......
Страница 230: ...4 16 Section 4 Advanced Capabilities...
Страница 274: ...This page is intentionally left blank 6 6 Section 6 Servo Tuning...
Страница 290: ...This page is intentionally left blank B 6 Appendix B Trouble Shooting and Maintenance...