
DG
get acquisition data
IMM PGM MIP
SYNTAX
DG
DESCRIPTION
This command is used to retrieve data acquired from a data acquisition request.
REL. COMMANDS
DC
-
setup data acquisition request
DE
-
enable / disable data acquisition
DD
-
data acquisition done status
EXAMPLE
DC1,1,0,4,1,500
nn2
=1 : Trigger axis is 1
nn3
=0
nn4
=4 : Position feedback from channel 3
nn6
=500 : Collect 500 samples
DE1
Enable data acquisition
DD
Query data acquisition done status
If true,
DEO
Disable data acquisition
DF
Get data acquisition sample count
DG
Get data collected
USAGE
♦
♦
PARAMETERS
None
RETURNS
This command returns byte wide binary data. Each four bytes represents one
DSP 32 bit word. The number of bytes returned depends on the setup request.
(See
DC
command).
DF -
data acquisition status, returns # of samples collected
nn1
=1 : Start data acquisition when trigger axis start motion
nn5
=1 : Collect data entry often servo cycle
1 = true 0 = false
500
Controller responds with number samples collected
3-48
Section
3
–
Remote
Mode
Содержание ESP300 Series
Страница 1: ...ESP300 Motion Controller Driver User s Manual...
Страница 4: ...ESP300 1999 EU Declaration of Conformity iv Preface...
Страница 29: ...This page is intentionally left blank Section 2 Modes of Operation 1 15...
Страница 30: ......
Страница 230: ...4 16 Section 4 Advanced Capabilities...
Страница 274: ...This page is intentionally left blank 6 6 Section 6 Servo Tuning...
Страница 290: ...This page is intentionally left blank B 6 Appendix B Trouble Shooting and Maintenance...