87
CHAPTER 8 FUNCTION
8
8.7 Shift Fu
nction
(4) Setting example of when both the scaling function and shift function are used
Ex.
When the following settings are used for a channel with output range of 0 to 5V:
• "CH
Scaling enable/disable setting": "0: Enable"
• "CH
Scaling upper limit value": 9000
• "CH
Scaling lower limit value": 3000
• CH
Shifting set value (RWw6 to RWw9): -25
The digital value is as follows:
Analog output
voltage (V)
Digital value
Digital value + Shifting set
value
Value after scaling
0
3025
3000
0
1
4225
4200
2400
2
5425
5400
4800
3
6625
6600
7200
4
7825
7800
9600
5
9025
9000
12000
Add the shifting set value.
Scale conversion
Digital value
1) Digital value
(before adjustment)
2) Digital value + Shifting set value
(after adjustment)
3) Scale converted value
1) Digital value
(before adjustment)
5
0
12000
0
3025
3000
9000 9025
Analog output voltage (V)
Add the shifting set value.
2) Digital value +
Shifting set value
(after adjustment)
3) Scale
converted
value