CHAPTER 8 FUNCTION
8
8.4 Analog Output H
O
LD
/CLEAR Fun
ction
(2) Setting procedure
1.
Set "Parameter write" for "Method selection".
"CC IE Field Configuration" window
Select a D/A converter module in "List of stations"
[CC IE Field Configuration]
[Parameter Processing of Slave Station]
2.
Set "CH
D/A conversion enable/disable setting" to "0: Enable".
3.
Set "CH
Analog output HOLD/CLEAR setting".