82
Ex.
2: When values are set for a channel with output range of -10 to 10V as follows:
• "CH
Scaling enable/disable setting": "0: Enable"
• "CH
Scaling upper limit value": 12000
• "CH
Scaling lower limit value": 4000
The digital values and scale-converted digital values are as follows:
Digital value
Digital value after scale
conversion
Analog output voltage (V)
4000
-16000
-10
6000
-8000
-5
8000
0
0
10000
8000
5
12000
16000
10
10V
-10V
Analog output voltage (V)
Scaling lower limit
value: 4000
Scaling upper limit
value: 12000
0
16000
-16000
8000
16383
-16384
Scale converted digital value
Digital value