138
(5) CH
Digital value (RWw2 to RWw5)
On this area, the digital value for D/A conversion is written, in signed 16-bit binary, from the CPU module.
*1
The setting range and the actual range of when the scaling function is enabled depend on the settings in the scaling
upper limit value and the scaling lower limit value.
(a) When a value out of the setting range is written
D/A conversion is performed with the upper and lower limit value of the setting range. Simultaneously, the
following status notifies that the setting is out of the range.
• The check code is stored in CH
Set value check code (RWr2 to RWr5).
For details on check codes, refer to the following.
• The error code (060
) for an out-of-range digital value is stored in Latest warning code (RWr1).
• Warning flag (RX7) turns on.
• The ALM LED flashes.
(b) Default value
The default value is set to 0 for all channels.
Output range setting
When the scaling function is disabled
When the scaling function
is enabled
*1
Setting range (Actual range)
Digital value when a value out
of the setting range is written
Setting range
0:
4 to 20mA
-288 to 12287
(Actual range: 0 to 12000)
12288 or more: 12287
-289 or less: -288
-32768 to 32767
(Maximum actual range: -32000
to 32000)
1:
0 to 20mA
2:
1 to 5V
3:
0 to 5V
4:
-10 to 10V
-16384 to 16383
(Actual range: -16000 to 16000)
16384 or more: 16383
-16385 or less: -16384
5:
User range setting 1
(-10 to 10V)
-12288 to 12287
(Actual range: -12000 to 12000)
12288 or more: 12287
-12289 or less: -12288
6:
User range setting 2
(0 to 20mA)
-288 to 12287
(Actual range: 0 to 12000)
12288 or more: 12287
-289 or less: -288
b15 b14 b13 b12 b11 b10 b9
b8
b7
b6
b5
b0
b1
b2
b3
b4
Sign bit
1: Negative
0: Positive
Data area