7 - 10 7 - 10
MELSEC-Q
7 DATA COMMUNICATION USING THE BIDIRECTIONAL PROTOCOL
7.1.3 Sequence program for data reception
This section explains the sequence program for data reception.
For details on the BIDIN instruction for data reception, see Chapter 10.
X3 Read request
Create control data from D0
G.BIDIN
Un
D0
D10
M0
M0
M1
(CH1)
Processing for normal completion
(stores receive data, etc.)
1)
2)
3)
4)
Reception data read
request (X3)
BIDIN instruction
BIDIN instruction complete device
BIDIN instruction complete 1
(Normal completion)
Receive data count (address: 600
H
)
Receive data(address: 601
H
to 7FF
H
)
Receive data
One scan
Response transmission
Data reception
Q series C24 ready (X1E)
BIDIN
(OFF)
m
n
1) Start the local station programmable controller.
The values specified with GX Developer are stored in the Q series C24.
2) When data is received from the external device, the reception data read request
(X3) turns ON.
3) After the control data for the BIDIN instruction is stored in the device, the sequence
program executes the BIDIN instruction and reads the receive data.
4) When the reading of receive data is completed, a response message (ACK
message when the operation was completed normally) is sent and the device that
has completed the BIDIN instruction turns ON.
Содержание MELSEC QJ71C24
Страница 1: ......
Страница 2: ......
Страница 103: ...3 42 3 42 MELSEC Q 3 SPECIFICATIONS MEMO ...
Страница 177: ...6 33 6 33 MELSEC Q 6 DATA COMMUNICATION USING THE NON PROCEDURE PROTOCOL MEMO ...
Страница 397: ...App 24 App 24 MELSEC Q APPENDIXES Connection example 3 Connection example 4 ...
Страница 441: ......
Страница 442: ......