11 - 27 11 - 27
MELSEC-Q
11 TROUBLESHOOTING
Protocol
Error code
(Hexa-
decimal)
Error
Description
Signal
name
Corrective action
MC
Non
Proce-
dure
Bidire-
ctional
Pre-
defined
7F68
H
Framing
error
•
Data does not match the stop bit
setting.
•
A malfunction occurred in the network
because the power source of the
partner station was on or off.
•
Noise occurs in the network.
•
When the multidrop was connected,
data was transmitted simultaneously by
multiple devices.
SIO
•
Match the Q series C24 and external
device settings.
•
Clear the error information according to
the ERR. clear request (YE/YF).
In addition, when communicating data
with the non procedure protocol,
execute the INPUT instruction, and
read and discard the unnecessary data.
•
Measure the noise.
•
When connecting the multidrop, remove
the interlock so that data will not be
transmitted simultaneously by multiple
devices.
7F69
H
Parity
error
•
Data does not match the parity bit
setting.
•
A malfunction occurred in the network
because the power source of the
partner station was on or off.
•
Noise occurs in the network.
•
When the multidrop was connected,
data was transmitted simultaneously by
multiple devices.
P/S
•
Match the Q series C24 and external
device settings.
•
Clear the error information according to
the ERR. clear request (YE/YF).
In addition, when communicating data
with the non procedure protocol,
execute the INPUT instruction, and
read and discard the unnecessary data.
•
Measure the noise.
•
When connecting the multidrop, remove
the interlock so that data will not be
transmitted simultaneously by multiple
devices.
7F6A
H
Buffer full error
•
OS receive buffer overflowed and
receive data was skipped.
SIO
•
Use DTR and DC control and perform
data communications so that the buffer
does not become full. (Perform RS
⋅
CS
control when the modem function is
used.)
•
If the Read Request signal was turned
ON, execute read immediately.
7F6B
H
CD(DCD) signal
control error
•
Data was received when CD(DCD)
signal is OFF when "CD terminal check
enabled" was designated.
CHn
ERR.
•
Recheck the CD(DCD) signal control of
the external device.
(Send while the CD(DCD) signal is ON.)
•
Set "no CD terminal checking" and
perform communication.
7F6C
H
Transmission
error
•
Data cannot be sent because the line is
not connected.
CHn
ERR.
•
Transmit data after line connection
processing on the interface side that
uses the modem function.
Содержание MELSEC QJ71C24
Страница 1: ......
Страница 2: ......
Страница 103: ...3 42 3 42 MELSEC Q 3 SPECIFICATIONS MEMO ...
Страница 177: ...6 33 6 33 MELSEC Q 6 DATA COMMUNICATION USING THE NON PROCEDURE PROTOCOL MEMO ...
Страница 397: ...App 24 App 24 MELSEC Q APPENDIXES Connection example 3 Connection example 4 ...
Страница 441: ......
Страница 442: ......