App. - 15 App. - 15
MELSEC-Q
APPENDIXES
Appendix 2.3.2 Installing the Q series C24 into existing systems
This section shows the notes when installing the Q series C24 into an existing system
that uses UC24/C24-S8.
(1) Data communication using m:n connection
When the Q series C24 is installed into an existing system that has an m:n system
structure between the programmable controller CPU and external devices, and
data communication is performed using the MC protocol, the following notes
should be considered:
(a) Accessing the programmable controller using a frame for form 5
When the UC24/C24-S8 is connected on the line, it is not possible to access
the programmable controller in the QnA compatible 4C frame (form 5) for
binary code communication.
(b) Data communication between external devices
1) When data communication is performed in order to link with an external
devices to perform a 1:1 communication with the programmable
controller CPU, it is necessary to change the station number (80
H
to A0
H
00
H
to 1F
H
) designated in the "Station number" and "Local station
number" items in the messages on the external device side. (It is not
necessary to specify this when an A compatible 1C frame is used.)
Alternatively, it is necessary to change the message frame so that it has
a data order different from that of the MC protocol.
• Station number: Designate the number of device to which data is sent
• Local station number: Designate the number of the device that sends
data
2) Perform the data communication according to the User's Manual
(Application).
(c) Processing reception data on the external device side
Set the external device so that it ignores the following reception messages
that are unrelated to the local station.
• The command message and the corresponding response message that
are sent from other stations when accessing the programmable controller
CPU using the MC protocol.
• Messages when accessing between external devices.
(2) Data communication using 1:n connection
When the UC24/C24-S8 is connected on the line, it is not possible to access the
programmable controller in the QnA compatible 4C frame (format 5) for binary
code communication.
POINT
Since performances and response speeds are different between the Q series C24
and the UC24/C24-S8, communication may not be performed normally when a
programmable controller module in the A series is replaced by a Q series
programmable controller.
When a module is changed to a Q series programmable controller module, make
sure to check operation.
Содержание MELSEC QJ71C24
Страница 1: ......
Страница 2: ......
Страница 103: ...3 42 3 42 MELSEC Q 3 SPECIFICATIONS MEMO ...
Страница 177: ...6 33 6 33 MELSEC Q 6 DATA COMMUNICATION USING THE NON PROCEDURE PROTOCOL MEMO ...
Страница 397: ...App 24 App 24 MELSEC Q APPENDIXES Connection example 3 Connection example 4 ...
Страница 441: ......
Страница 442: ......