3 - 33 3 - 33
MELSEC-Q
3 SPECIFICATIONS
Address
Decimal (Hex)
Protocol
CH1 CH2
Application Name
Initial
value
MC Non Bi Pd
Registration
Reference
section
8206
(200E
H
)
For designation
of modem
function -3
Circuit disconnect wait time (programmable controller CPU watch
use)
0000
H
to FFFF
H
: Wait time (unit: s)
0
RW
—
Allowed
Section 9.4.4
User's Manual
(Application)
8207
(200F
H
)
8456 to
8463
(2108
H
to
210F
H
)
Use prohibited
System area
—
Receive interrupt-issued designation
8208
(2010
H
)
8464
(2110
H
)
Interrupt
designation
0: Do not issue interrupt.
1: Issue interrupt.
0 — RW — Allowed
User's Manual
(Application)
8209
(2011
H
)
8465
(2111
H
)
Use prohibited
System area
—
8210
(2012
H
)
8466
(2112
H
)
Transmission control start free area designation
64 to 4,095: transmission control start free area
64
8211
(2013
H
)
8467
(2113
H
)
Transmission control end free area designation
263 to 4096: transmission control end free area
263
RW
User’s Manual
(Application)
Non procedure and non reception monitoring time format
designation
8212
(2014
H
)
8468
(2114
H
)
For transmission
control
designation
0: Format-0
1: Format-1
0
—
RW
—
Allowed
User’s Manual
(Application)
8213 to
8215
(2015
H
to
2017
H
)
8469 to
8471
(2115
H
to
2117
H
)
Use prohibited
System area
—
8216
(2018
H
)
8472
(2118
H
)
Communication data monitoring designation
0000
H
: No monitor/stopped monitor designation
0001
H
: Monitor start designation
0002
H
: Monitoring (Q series C24 is a set.)
1002
H
: Monitoring stopped (Q series C24 is set.)
100F
H
: Monitor setting error (Q series C24 is a set.)
0
8217
(2019
H
)
8473
(2119
H
)
Data optional designation
0: Off 1: On
Full stop designation (b0)
Timer 0 errors at occurrence stop designation (b2)
For system (b1), (b3) to (b15)
0
8218
(201A
H
)
8474
(211A
H
)
Monitor buffer head address designation
(400
H
to 1AFD
H
,2600
H
to 3FFD
H
)
CH1:
2600
H
CH2:
3300
H
(
3)
8219
(201B
H
)
8475
(211B
H
)
Communication
data monitoring
function
Monitor buffer size designation
(0003
H
to 1A00
H
)
0D00
H
RW Allowed
User’s Manual
(Application)
8220 to
8223
(201C
H
to
201F
H
)
8476 to
8479
(211C
H
to
211F
H
)
Use prohibited
System area
—
User frame receive format designation (1st to 4th)
8224 to
8227
(2020
H
to
2023
H
)
8480 to
8483
(2120
H
to
2123
H
)
0: Format-0,
1: Format-1
8228 to
8231
(2024
H
to
2027
H
)
8484 to
8487
(2124
H
to
2127
H
)
For designation
of user frame
receiving method
Exclusive format-1 received data count (1st to 4th)
0 or more: Exclusive format-1 received data count
0
—
RW
—
Allowed
Section 9.4.7
User's Manual
(Application)
8232 to
8239
(2028
H
to
202F
H
)
8488 to
8495
(2128
H
to
212F
H
)
Use prohibited
System area
—
Transmission transparent code designation (2nd to 4th)
0000
H
Other than 0000
H
:No designation
:Designated (below)
8240 to
8248
(2030
H
to
2038
H
)
8496 to
8504
(2130
H
to
2138
H
)
For designation
of transparent
code
• Transparent code (b0 to b7)
00
H
to FF
H
: Transparent code
• Additional code (b8 to b15)
00
H
to FF
H
: Additional code
0
—
RW
—
Allowed
Section 9.4.5
User's Manual
(Application)
8249 to
8255
(2039
H
to
203F
H
)
8505 to
8511
(2139
H
to
213F
H
)
Use prohibited
System area
—
Содержание MELSEC QJ71C24
Страница 1: ......
Страница 2: ......
Страница 103: ...3 42 3 42 MELSEC Q 3 SPECIFICATIONS MEMO ...
Страница 177: ...6 33 6 33 MELSEC Q 6 DATA COMMUNICATION USING THE NON PROCEDURE PROTOCOL MEMO ...
Страница 397: ...App 24 App 24 MELSEC Q APPENDIXES Connection example 3 Connection example 4 ...
Страница 441: ......
Страница 442: ......