11 - 20 11 - 20
MELSEC-Q
11 TROUBLESHOOTING
Protocol
Error code
(Hexa-
decimal)
Error
Description
Signal
name
Corrective action
MC
Non
Proce-
dure
Bidire-
ctional
Pre-
defined
7164
H
Request
error
•
Either the request or the device
designation method is wrong.
⎯
•
Check the transmission
message/request from the external
device, make the necessary
corrections, and send again.
7166
H
System
error
•
The OS of the Q series C24 detected
some error.
⎯
(
1)
7167
H
•
A write command was designated when
"Disable write during RUN" was set.
C/N
•
Change the setting to "Enable write
during RUN" and restart data
communications.
7168
H
Cannot execute a
command during
RUN
•
A command that cannot be executed
during RUN was designated.
C/N
•
Stop the CPU and restart data
communications.
7169
H
CPU
error
•
Cannot communicate normally with the
CPU.
C/N
•
If there is an error in the CPU, remove
the CPU error and restart data
communications.
716A
H
to
716B
H
System error
•
The OS of the Q series C24 detected
some error.
⎯
(
1)
•
The Q series C24 used is not
compatible with the Built-in Ethernet
port QCPU.
•
To use a Built-in Ethernet port QCPU,
use a Q series C24 of function version
B or later, and the first 5 digits of its
serial No. must be 10042 or greater.
716C
H
System
error
•
The OS of the Q series C24 detected
some error.
⎯
(
1)
716D
H
•
Monitor data was not written using QnA
compatible 2C/3C/4C frame.
PRO
716E
H
Monitor data write
error
•
Monitor data was not written using A
compatible 1C frame.
PRO
•
Rewrite monitor data.
716F
H
Device
error
•
A nonexistent device was designated.
•
Device that cannot be specified by the
corresponding command was
designated.
PRO
•
Check and correct the external device
transmit message and restart data
communications.
7170
H
•
Number of access points exceeded the
range.
PRO
7171
H
•
A device that cannot be designated was
designated.
PRO
7172
H
A compatible 1C
frame error
•
Written number of monitoring points is
incorrect. For example, [0] was
designated.
PRO
•
Check and correct the external device
transmit message and restart data
communications.
7173
H
Monitor data write
error
•
Monitor data was written for a CPU
other than a Q/QnACPU using QnA
compatible 2C/3C/4C frame.
PRO
•
Write the monitor data and use the A
compatible 1C frame to a CPU other
than a Q/QnACPU.
7D00
H
Protocol No. setting
error
•
In control data of the CPRTCL
instruction, the specified protocol No. is
out of range.
CHn
ERR.
•
Correct the protocol No. setting.
7D01
H
Continuous protocol
execution count
setting error
•
The number of protocols to be executed
continuously, which is specified with an
argument in the CPRTCL instruction, is
out of range.
CHn
ERR.
•
Correct the value set for the number of
protocols to be executed continuously.
7D02
H
Protocol not-ready
error
•
The protocol was executed while Pre-
defined protocol ready (X1D) is OFF.
•
The CPRTCL instruction was executed
during protocol setting data writing.
•
The CPRTCL instruction was executed
with abnormal protocol setting data.
CHn
ERR.
•
Confirm Pre-defined protocol ready
(X1D) turned ON before executing the
CPRTCL instruction.
•
To prevent concurrent execution of the
CPRTCL instruction, set the CPU to
STOP before writing the protocol setting
data.
•
Write the protocol setting data again to
the Q series C24N, and then execute
the CPRTCL instruction.
•
If this error persists even after rewriting,
replace the module.
Содержание MELSEC QJ71C24
Страница 1: ......
Страница 2: ......
Страница 103: ...3 42 3 42 MELSEC Q 3 SPECIFICATIONS MEMO ...
Страница 177: ...6 33 6 33 MELSEC Q 6 DATA COMMUNICATION USING THE NON PROCEDURE PROTOCOL MEMO ...
Страница 397: ...App 24 App 24 MELSEC Q APPENDIXES Connection example 3 Connection example 4 ...
Страница 441: ......
Страница 442: ......