11 - 49 11 - 49
MELSEC-Q
11 TROUBLESHOOTING
11.3.13 Communication is intermittent.
Symptom Cause
Corrective
action MC
B
idi
rec
tional
Non
proc
edure
P
re-def
ined
• With a multidrop link, two or
more devices transmitted
data at the same time.
• Connect the external devices and the Q series C24 in
a 1:1 configuration and perform a communications
test. Since data is transmitted simultaneously from
two or more devices with a multidrop link when
normal communications among all the devices is
possible, interlock the external devices so that they do
not transmit simultaneously.
• The signal cable wiring
connection is faulty.
• Replace the cable, or make the connections firm.
• When "Check CD terminal" is
set, the CD(DCD) signal is
turned on/off repeatedly.
• Change the wiring so that the CD(DCD) signal
remains ON all the time, or change the setting to "Do
not check CD terminal".
• When half-duplex
communications is selected,
the ON/OFF timing of each
signal is not matched.
• Control the external device so that the ON/OFF
timing of each signal is matched.
See User's Manual (Application).
• Requested processing of the
next transmission before the
processing of the current
transmission is completed.
• Requested processing of the
next reception before the
processing of the current
reception is completed.
• Make sure to obtain handshake in the sequence
program.
• Communication via modem
is disrupted.
• Since communication via modem may be disrupted
due to low line quality or instantaneous interruption,
create a sequence program for reconnecting the line
in case of unexpected line disruption.
If this symptom occurs frequently, reduce the
communication speed of the modem, and retry the
communication.
• Communications are
intermittently
established and lost.
( 1)
• The data sent from the Q
series C24 are received
back on the RS-422/485
interface (CH2) side.
• Disable the echo back in the Echo back
enable/disable setting before communication.
1 The following explains how to take corrective actions when a normal exit response
message cannot be received upon sending of a command message.
(a) When a response message of abnormal end is received
1) When an external device sent a command message and received an
abnormal end response message, take corrective action with the error
according to the error code in the response message (see Section 11.2).
Содержание MELSEC QJ71C24
Страница 1: ......
Страница 2: ......
Страница 103: ...3 42 3 42 MELSEC Q 3 SPECIFICATIONS MEMO ...
Страница 177: ...6 33 6 33 MELSEC Q 6 DATA COMMUNICATION USING THE NON PROCEDURE PROTOCOL MEMO ...
Страница 397: ...App 24 App 24 MELSEC Q APPENDIXES Connection example 3 Connection example 4 ...
Страница 441: ......
Страница 442: ......