6 - 10 6 - 10
MELSEC-Q
6 DATA COMMUNICATION USING THE NON PROCEDURE PROTOCOL
2) Reception by received data count
If a specified receive data count is too large for the receive data storage
area, Receive buffer memory length (address: A7
H
/147
H
, default: 512
words) minus 1 is used as the receive data count instead.
(Receive data storage area) > (Data length received from external device)
(Example) When 550 words of data is received through the CH1 interface
in three parts when the CH1 interface receive area consists of
addresses 600
H
to 7FF
H
(default value)
External device
Reception data read
request X3
511 words
Sequence program
INPUT
INPUT
39 words
INPUT
472 words
78 words
433 words
117 words
1st data
2nd data
3rd data
Read data....
1st 511 words
Read data....
1st 39 words and
2nd 472 words
Q series C24