C-66
11.2 Connecting the power supply cable
1. Remove the screws and the control box cover
LGH-15 to 100 RX
5
(1) Tighten the ground wire and transmission cables to the ter-
minal block.
(2) Secure the transmission cables using the cord clips.
Upon completion of the wiring connections, replace the control
box cover.
CAUTION:
• Always separate the power supply cable and transmission
cable by 5 cm or more to prevent malfunctioning of the unit.
• If the length of the stripped power cables wires is too long,
the conductors may touch and short out.
• Power supply cable size : 1.5mm
2
or more.
LGH-150 and 200 RX
5
Screw
Control box cover
Pass the power cable through the bush* and connect to the
TM1 terminal block using the round terminals. Connect the
ground wire to the ground terminal and secure tightening the
bush. (*: for PG connector or the like)
LGH-15 to 100 RX
5
Power supply cable
Power supply cable
Cord clip
Insert the cutting
TM1
Bush
PG connector
Ground wire
Transmission cable
Ground wire
TM1
Insert the cutting
Bush
Power supply cable
PG connector
Cord clips
The following system configuration can be created. Connect the necessary parts.
1. When connecting with remote controller (PZ-60DR-E, PZ-41SLB-E).
2. When interlocked with indoor unit of air conditioner or other external device including other manufactures.
3. When interlocking with a pulse output device.
4. When operating multiple Lossnay units.
5. When take malfunction monitor output, or take By-pass operation monitor output.
6. When connect to an Electrically operated damper, or take operation monitor output.
7. When switching High / Low / Extra-Low speed externally (when CO
2
sensor or other device is connected).
8. When switching By-pass externally.
9. When using the remote/local switching and the ON/OFF input (level signal)
10. When connecting to the City Multi, Lossnay remote controller (PZ-52SF-E) or Mitsubishi Electric Air-Conditioner
Network System (MELANS).
CAUTION:
• When connecting external devices (electrically operated damper, lamp, monitoring unit, etc.) using output signals of the
Lossnay unit, make sure to install safety equipment for the external devices. (It could cause fire, damage, etc. without safety
equipment.)
LGH-150 and 200 RX
5
Control box cover
Control box cover
Screw
2. Connecting the power supply cable and transmission cable