C-42
When an outdoor temperature of 28ºC has not
been detected within 24 hours
0
5
10
15
20
25
30
35
40
0
5
10
15
20
25
30
35
40
Indoor temperature ºC
24ºC
Lossnay
Ventilation
When an outdoor temperature of 28ºC has been
detected within 24 hours
0
5
10
15
20
25
30
35
40
0
5
10
15
20
25
30
35
40
Indoor temperature ºC
Lossnay
Ventilation
24ºC
Bypass ventilation
Prohibition temperature 8ºC
Bypass ventilation
Prohibition temperature 8ºC
Outdoor temperature ºC
Outdoor temperature ºC
Undetermined area
When operation starts under this condition, Lossnay ventilation will be activated.
When this condition is reached after operation starts, the current ventilation mode is maintained.
Lossnay ventilation area
Bypass ventilation area
Undetermined area
Bypass
Ventilation
Undetermined area
Bypass
Ventilation
The map will differ depending on the operation mode that has been set with the A-control remote controller
or the K-control remote controller for Mr. Slim, or the MA remote controller or the ME remote controller for
City Multi indoor units. There will be switching to the ventilation mode in conjunction with the set tempera-
ture of the air conditioner remote controller. Note that the “b” map will be followed while Mr. Slim and City
Multi indoor units are stopped.
Cooling mode (Winter)
0
5
10
15
20
25
30
35
40
0
5
10
15
20
25
30
35
40
Indoor temperature ºC
Heating mode (Summer)
0
5
10
15
20
25
30
35
40
0
5
10
15
20
25
30
35
40
Indoor temperature ºC
Remote controller
Set temperature
Bypass ventilation
Prohibition temperature 8ºC
4ºC
Lossnay
Ventilation
Lossnay
Ventilation
Remote controller
Set temperature
Outdoor temperature ºC
Outdoor temperature ºC
Undetermined area
When operation starts under this condition, Lossnay ventilation will be activated.
When this condition is reached after operation starts, the current ventilation mode is maintained.
Lossnay ventilation area
Bypass ventilation area
Undetermined area
Bypass
Ventilation
Bypass
Ventilation
Undetermined area
Bypass
Ventilation
Undetermined area
a. Systems interlocked with Mr. Slim and City Multi indoor units
Pattern 1. Normal ventilation mode
When PZ-60DR-E is used, operation will be at the setting of automatic ventilation adjustment pattern “1”
of the remote controller function selection. When PZ-60DR-E is not used, operation will be at the OFF
setting of function selection switch (SW2-7) on the Lossnay circuit board.
b. When there is no interlocking with Mr. Slim and City Multi indoor units
Содержание LGH-100RX5 -E
Страница 1: ...Lossnay Remote Controller ...
Страница 2: ......
Страница 94: ...C 94 ...
Страница 95: ...C 95 5 ...
Страница 96: ...C 96 ...
Страница 97: ...C 97 ...
Страница 98: ...C 98 5 3 ...
Страница 99: ...C 99 ...
Страница 106: ...Y08 004 Jan 2009 MEE ...