SW1: When this is ON, Lossnay cannot turn ON/OFF by the
RemoteController (PZ-60DR-E, PZ-52SF-E).
SW2: When SW1 is ON, Lossnay can be turned ON by setting
SW2 at ON or turned OFF by setting SW2 at OFF.
SW1: Remote/local selector switch
SW2: ON/OFF switch
X, Y : Relay (Contactor rating DC 1 mA)
• One shielded wire is connected to TB5
S
on the PCB on ter-
minal. Address setting is required. (Refer to function setting
section C-72.)
M-NET transmission cable:Connect any of the City Multi indoor
unit, or Mitsubishi Electric Air-
Conditioner Network System
(MELANS) - to the Lossnay.
• Connecting positions are different for the Remote Controller
PZ-60DR-E and PZ-52SF-E.
PZ-60DR-E:
Connect to TM4
1
,
2
on the PCB. (Refer to C-67) “When
connecting with Remote Controller (PZ-60DR-E)”.)
PZ-52SF-E:
Connect to TB5
A
,
B
on the same terminal block as for
the M-NET transmission wires.
• Securely connect the M-NET transmission wires to TB5
A B
. (No-Polar)
Type: (Shielded wire, CVVS/CPEVS)
Wire diameter: 1.25 mm
2
to 2.0 mm
2
CAUTION:
• Don’t tighten screws on the terminal block with a torque larg-
er than 0.5 Nm. It may damage the PCB.
• Always use shielded wires only for the M-NET transmission
wires, and finish the shield properly.
Remote ON/OFF
adaptor (Optional)
PAC-SA88HA-E
Lossnay
control board
CN32
SW1
SW2
Y
X
Y
X
Remote control
board
Max wiring length 10 m
Relay circuit
Orange 1
Red 2
Brown 3
Relay power supply
S
B
A
TB5
M-NET transmission cable
Shielded wire
M-NET transmission cable input terminal block
9.When using the remote/local switching and the ON/OFF input (level signal)
The remoto controller (PZ-41SLB-E) cannot be used.
Insert the optional remote ON/OFF adaptor (PAC-SE55RA-E) in CN32 on the Lossnay control PCB.
10.When connecting to the City Multi, Lossnay remote controller (PZ-52SF-E) or
Mitsubishi Electric Air-Conditioner Network System (MELANS)
* If centralized control is performed according the wire connection shown in this section, the remote controller (PZ-41SLB-E)
cannot be used.
When interlocking with Mitsubishi Free Plan air conditioner
When connecting to PZ-60DR-E and MELANS
M-NET transmission cable
Lossnay
Air
conditioner
Air
conditioner
MA remote
controller
PZ-60DR-E
M-NET transmission cable
Lossnay
Air
conditioner
Air
conditioner
MA remote
controller
PZ-52SF-E
• Incase of PZ-60DR-E
• Incase of PZ-52SF-E
Power
supply unit
Lossnay
MELANS
M-NET transmission cable
(Optional)
PZ-60DR-E
* Limit the total length of transmission wires no longer than
500 m. Limit the wiring length between Lossnay and the
power supply unit (Optional) or the outdoor unit no longer
than 200 m.
• Connect the power feeding unit.