C-7
Use Lossnay remote controller PZ-60DR-E .
(Do not use PZ-41SLB-E).
Lossnay transmission connection terminal
Two remote controller system with multiple Lossnay units
●
It is also possible to operate two remote controller units when using mul-
tiple Lossnay units.
Power supply
Power supply
Remote controller
PZ-60DR-E or
PZ-41SLB-E
Interlocking multiple units
When the operation signal is an uncharged a-contact signal
Interlocking/individual combined systems
Interlock settings are possible with the inclusion of a group setting.
(Joint use of the air conditioner remote controller and Lossnay remote
controller is possible.)
●
Interlocking is possible from multiple air conditioning units, etc.
(excluding pulse input)
(Separately sold parts are necessary depending on the operation signal).
●
Applicable indoor units are C type or later (for use with MA remote con-
troller) models
●
Set the different groups of indoor unit of air conditioner and Lossnay unit.
●
When the address number has been changed, the data in the memory is
automatically reset.
Power supply
Power supply
Power supply
Power supply
Lossnay
A/C
A/C
A/C
Air conditioning
unit side remote
controller
Air conditioning
unit side remote
controller
Air conditioning
unit side remote
controller
Remote controller
PZ-60DR-E or
PZ-41SLB-E
Indoor unit of
air conditioner
(01)
Centralized
controller
(000) Outdoor
unit (51)
Operation settings
MA remote
controller
Lossnay (02)
Lossnay remote
controller
(PZ-60DR-E)
Group 1
Group 2
Use Lossnay remote controller PZ-60DR-E or PZ-41SLB-E .
(Do not use PZ-52SF-E).
Lossnay transmission connection terminal
TM4
2
1
PZ-60DR-E
Remote controller input terminal
Transmission wires
Lossnay
(Main)
Remote controller
(PZ-60DR-E or PZ-41SLB-E)
Power
supply
External
device
Operating switch
for external device
Lossnay (Sub)
MAX 15 units
Power
supply
Lossnay (Sub)
Power
supply
Power
supply
Connect to
remote
controller
(PZ-60DR-E)
Connect
to third
Lossnay
Main/Sub selection
switch
(SW1)
Main Sub
2
1
2
1
Transmission cable
First Lossnay
Second
Lossnay
TM4
(Factory setting: main)
TM4
S
B
A
TB5
M-NET
transmission cable
and PZ-52SF-E
Shielded wire
M-NET transmission cable
input terminal block
TM4
2
1
PZ-60DR-E
Remote controller
input terminal
Transmission wires
SA1
SA2
10 digit
1 digit
Address setting switch
Setting
Change the setting on the main/sub switch (SW1) on the second
and subsequent Lossnay units to “Sub”.
Address Setting