C-23
5.1
External Control Operating Mode Selection
There are four modes when operating using signals from external equipment.
1. ON/OFF interlock (the chosen function from either external signal or remote control switch has priority)
2. ON interlock
3. OFF interlock
4. External priority ON/OFF interlock
Operating Signal
Mode
ON/OFF
inter-
lock
ON
inter-
lock
OFF
inter-
lock
External
priority
ON/OFF
inter-
lock
This mode does not exist.
When external signal is level signal.
When external signal is pulse signal.
(Optional setting)
External signal
Remote controller
[ON/OFF] button pressed
Operating
condition
Operating
Stopped
External signal
Remote controller
[ON/OFF] button pressed
Operating
condition
Operating
Stopped
External signal
Remote controller
[ON/OFF] button pressed
Operating
condition
External signal
Remote controller
[ON/OFF] button pressed
Operating
condition
External signal
Remote controller
[ON/OFF] button pressed
Operating
condition
Operating
Stopped
Operating
Stopped
External signal
Remote controller
[ON/OFF] button pressed
Operating
condition
Operating
Stopped
Operating
Stopped
External signal
Remote controller
[ON/OFF] button pressed
Operating
condition
Operating
Stopped
Setting Method
When PZ-41SLB-E is used, use the remote controller to set. (Refer to page C-91)
When PZ-41SLB-E is not used, use the DIP switch 5-7,8 to set. (Refer to page C-76)