12.7 Test Run
6. Wiring hole for installing directly on the wall (or open wiring)
•
Cut off the shaded area from the upper cover using a knife, nippers, etc.
•
Take out the remote control cord connected to the terminal block via this portion.
7. Install the cover to the remote controller.
First, hook the cover to the two upper claws and then fit it to the remote controller.
CAUTION Press the cover until it snaps shut. If not, it may fall off.
NOTE: A protection sheet is stuck to the operation section. Peel off this protection sheet before use.
Operation
Relevant button
Relevant display items
Sequence
1. Starting the Lossnay unit
Operation lamp
“High”
Press the [
ON/OFF] button and confirm that the Operation lamp turns on.
2. Setting the ventilation mode
“HEAT EX.” non-automatic
Press the Function selector button: Each time it is pressed, the corresponding display
will change in accordance with the sequence [HEAT EX.] (non-automatic) --> [BY-
PASS] (non-automatic) --> [AUTO].
3. Selecting the fan speed
“Low” “Extra High”
Press the Fan Speed Adjustment button to select either Low or High (Extra High) fan
speed. High and Extra-High can be selectable by initial setting.
4. Selecting the Extra Low fan
speed*
1
*
2
“Extra Low”
Press the “Extra Low” fan speed button.
Extra low operation will begin. Pressing the Fan Speed Adjustment button will cause
the fan speed to revert to its original speed (before the Extra low mode began).
Pressing the Extra Low fan speed button again will return operation to Extra low mode.
5. Stopping the Lossnay unit
Operation lamp
Press the [
ON/OFF] button.*
2
(Press the [
ON/OFF] button to turn off the Operation lamp.)
*
1
If you press a button for a feature that is not installed at the Lossnay unit, the remote controller will display the “NOT AVAILABLE” message.
*
2
If set to “24-hour Ventilation”, pressing the [
ON/OFF] button will cause this to be displayed in the dot display “24HR VENTILATION”, and the operation will switch to
Extra low fan speed mode. To stop operation, press the [
ON/OFF] button twice within 3 seconds, or press and hold the [
ON/OFF] button for 5 seconds.
If error code is displayed, refer to the following table.
Error code
Cause
Action
0900
The SW2 trial-operation switch from the Lossnay controll box
is On.
Turn off the trial-operation switch.
6608
If two or more Lossnay units are used together, “6608” may
indicate that the correct setting has not been performed using
the main/sub switches.
Turn off the power supply and use the main/sub switches to
specify one Lossnay unit as the main and the others as sub.
Turn the power supply back on. Note that all Lossnay units are
specified as main before shipment from the manufacturing plant.
If two remote controllers are used together, “6608” may
indicate that one of the controllers is not connected.
Turn off the power supply, connect the remote controller, then turn
the power supply back on.
If two remote controllers are used together, “6608”
may indicate that both of these controllers are not set
automatically when the power is turned on.
Turn off the power supply, then turn it back on.
Multiple transmission cables are wired with multi core cables.
For the applied transmission cable, wire the transmission cables
away from the other transmission cable.
Communication error (M-NET side)
Turn off the power supply and contact the distributor.
4116
A circuit error has occurred in the Lossnay unit.
3126
Temperature error (OA side).
5101
An error has occurred in the Lossnay thermistor (OA side).
5102
An error has occurred in the Lossnay thermistor (RA side).
3602
An error has occurred in the damper motor.
6600
Multiple address error (M-NET side)
6602
6603
6606
6607
Communication error (M-NET side)