11.4 Function settings
Address setting is requiered when connecting to City Multi, Lossnay remote controller (PZ-52SF-E) and MELANS.
11.4.1 Setting the address
Use the following procedure when setting the address for dedi-
cated Lossnay.
(The method in determining the addresses will depend on the
existing system. Refer to the appropriate technical documents
for details.)
(1) Remove the control box cover.
(1) Use a flatblade screwdriver to turn the address setting
switch on the circuit board.
• SA1 indicates the 10 digit and SA2 indicates the 1 digit.
• The factory setting is "00"
* When the address number has been changed, the
data in the memory is automatically reset.
LGH-50 and 100RX types
11.4.2 Changing the function selection switches (SW-2 and 5)
Set the selection switches (SW-2 and 5) to perform the appropriate function.
* The function marked (*) above can be set also from the remotecontroller (PZ-60DR-E). If the function is switched later using
the remote controller, it operates according to the setting on the remote controller.
1
2
3
4
5
6
7
8
9
10
(SW2)
1
2
3
4
5
6
7
8
9
10
(SW5)
Trial operation
Pulse input setting *
Power supply/exhaust when operation starts *
SA fan fixed at Low speed *
EA fan fixed at Low speed *
Power supply ON/OFF *
Bypass ventilation priority at Automatic mode *
Setting for TM4
9 10
output
Supply Extra High/High *
Exhaust Extra High/High *
Delay setting *
Operation monitor output *
Auto restoration after power failure *
Filter maintenance indication setting *
Setting for TM3
6 7
output
Interlock mode setting *
Exhaust fan stop at outdoor air lower than -15 C
Not used OFF: LGH-15 to 100RX
5
5
ON : LGH-150 and 200RX
Exhaust fan stop during defrosting *
Exhaust fan at Low speed at outdoor air lower than -15 C
}
1. Settings for pulse input
2. Switching to power supply/exhaust when operation starts
3. Switching to the multi ventilation mode
4. Power supply ON/OFF function (cannot be set when PZ-41SLB-E is used)
5. By-pass automatic ventilation priority setting *
6. Setting for TM4
90
output
7. Extra High/High switch setting
8. Set for delay operation at heating or cooling start-up
9. Operation output monitor
10. Exhaust fan stop during defrosting, exhaust fan Low speed operation at outdoor air lower than -15°C
11. Settings for automatic recovery following power supply interruption (cannot be set when PZ-41SLB-E is used)
12. Settings for filter cleaning (cannot be set when PZ-41SLB-E is used)
13. Setting for TM3
67
output
14. Settings for interlock mode
15. Exhaust fan stop at outdoor air lower than -15°C *