C-41
Stand-alone/multi-
ple Lossnay and
Lossnay remote
controller: PZ-
41SLB-E
Basic System
M- NET Control
Fixed to automatic ventilation.
Fixed to automatic ventilation.
Lossnay remote controller
PZ-60DR-E
The “Function selector” button of the remote controller
permits ventilation mode switching for automatic , Loss-
nay, and bypass ventilation. Bypass ventilation is set at
the time of night purge operation, and ventilation mode
switching is not possible.
Stand-alone/multi-
ple Lossnay and
Lossnay remote
controller: PZ-
60DR-E
Lossnay remote controller
PZ-52SF-E
The “Function selector” button of the remote controller
permits ventilation mode switching for automatic , Loss-
nay, and bypass ventilation.
Stand-alone/multi-
ple Lossnay and
Lossnay remote
controller: PZ-
52SF-E
M-NET controller
The “Operation mode” button of the system remote con-
troller and the centralized controller permits ventilation
mode switching for automatic , Lossnay, and bypass
ventilation.
(The schedule timer, ON/OFF remote controller, and the
group remote controller do not permit ventilation mode
selection.)
M-NET
Lossnay central
control system
ME remote controller
PAR-F27MEA,
MA remote controller
PAR-20/21MAA
M-NET
System interlocked
with City Multi
indoor units
System
Lossnay remote controller
PZ-60DR-E
The “Function selector” button of the remote controller
permits ventilation mode switching for automatic, Loss-
nay, and bypass ventilation. Bypass ventilation is set at
the time of night purge operation, and ventilation mode
switching is not possible.
Stand-alone/multi-
ple Lossnay and
Lossnay remote
controller: PZ-
60DR-E
Lossnay remote controller
PZ-41SLB-E
The “Function selector” button of the remote controller
permits ventilation mode switching for automatic, Loss-
nay, and bypass ventilation.
A-control remote controller
K-control remote controller
(Remote controller connection
prohibited with Lossnay )
Fixed to automatic ventilation.
System interlocked
with Mr. Slim
None
Level signal/pulse
signal output
device and external
device only
Remote controllers
System controllers
Ventilation mode
3
Bypass ventilation prohibited
When the conditions described below are applicable, the ventilation mode will be fixed at Lossnay ventilation.
When bypass ventilation has been set from the remote controller or the system controller, damper operation
will be set to Lossnay ventilation, even though bypass ventilation is displayed on the ventilation mode display.
●
When the outdoor temperature is 8ºC or lower. (Product condensation prevention)
When bypass ventilation prohibition has been set under this condition, the prohibition will be cancelled
when the outdoor temperature goes from a temperature of less than 10 ºC to one higher than 10ºC.
●
When there is an outdoor temperature (Outdoor Air) thermistor fault.
●
When, in the automatic ventilation mode, there is an outdoor temperature (Outdoor Air) or indoor tempera-
ture (Return Air) thermistor fault.
●
When Lossnay is set to the automatic ventilation mode and interlocked with Mr.Slim or City Multi indoor units
set to the fan operation mode.
4
Damper operation
The damper provides control with a 30 second period. Accordingly, a delay of 30 seconds maximum may be
generated from ventilation mode switching to damper operation.
5
Automatic ventilation algorithm temperature map
Ventilation mode switching of Lossnay ventilation/Bypass ventilation in the automatic ventilation mode is in
accordance with the following map.