C-51
No.
Error
Cause
Action
«
Check the power to Lossnay.
«
Check the address registration
of PZ-52SF-E with MELANS
(“HO” displays for 3 to 10 min-
utes when power is supplied to
the system).
«
Connect the transmission cable
to TB5
A
,
B
.
«
Check the Lossnay registration
with PZ-52SF-E.
«
Verify the address (SA1, SA2)
and register them again.
«
Make connections within the
transmission cable power supply
restrictions of the outdoor units,
or the power supply units.
(Refer to page C-31.)
«
Perform group setting again.
8
The remote controller
PZ-52SF-E continues to
blink “HO” when the
power is supplied to the
system.
«
The specified power is not supplied to Lossnay.
«
Group setting of the PZ-52SF-E address has
not been performed with MELANS.
«
Group setting has been performed with PZ-
52SF-E.
«
The M-NET transmission cable is connected to
TM4
1
,
2
.
«
For a Lossnay individual system with no
MELANS, Lossnay registration has not been
performed by PZ-52SF-E.
«
Lossnay address setting (SA1, SA2) is wrong.
«
Lossnay address setting (SA1, SA2) was changed.
«
The transmission cable power supply restric-
tions have been exceeded.
«
Group setting has not been performed after
replacement of the circuit board.
9
“LC 6608” appears on
the remote controller and
the Lossnay does not
operate.
«
PZ-60DR-E is connected to the terminal block
(TB5
A
,
B
) for the M-NET transmission
cable.
«
Rather than PZ-52SF-E, PZ-41SLB-E is con-
nected to the M-NET transmission cable.
«
When using PZ-60DR-E, con-
nect to the terminal block (TM4
1
,
2
) for the remote controller
transmission cable.
«
Change to the PZ-60DR-E or PZ-
52SF-E remote controller.
(PZ-41SLB-E cannot be used
with the M-NET.)
10
The operation from
MELANS and Lossnay
operation differ.
«
PZ-41SLB-E is connected to Lossnay.
«
PZ-60DR-E is connected by crossover cable
with multiple Lossnay units of a separate
group.
«
Change to the PZ-60DR-E or PZ-
52SF-E remote controller.
(PZ-41SLB-E cannot be used
with the M-NET.)
«
Do not connect PZ-60DR-E with
multiple Lossnay units of a sepa-
rate group.
Note: PZ-60DR-E and PZ-52SF-E cannot be used in the same group.