C-89
[1] Change Language
The language that appears on the dot display can be selected.
• Press the [
MENU] button to change the language.
Japanese (
) (ja), English (en), German (de), Spanish (es),
Russian (ru), Italian (it), Chinese (zh), French (fr)
[2] Function limit
(1) Operation function limit setting (operation lock)
To switch the setting, press the [
ON/OFF] button.
Dot display
Display
Function
Check
oFF
Operation lock setting is not made.
(Factory setting)
no1
Operation lock setting is made on all buttons
other than the [
ON/OFF] button.
no2
Operation lock setting is made on all
buttons.
* To make the operation lock setting valid on the normal screen, it is necessary to
press buttons (Press and hold down the FILTER and [
ON/OFF] buttons at
the same time for 2 seconds.) on the normal display after the above setting is
made.
* The same operation is used to cancel the lock.
(2) 24-hour ventilation setting
Sets whether to stop operation completely or initiate Extra low
operation by pressing the [
ON/OFF] button during operation. 24-
hour Ventilation cannot be set when the pulse input setting is ON in
the interlocking settings.
To switch the setting, press the [
ON/OFF] button.
Dot display
Display
Function
Check
oFF
Pressing the [
ON/OFF] button during
operation stops operation. (Factory setting)
on
Pressing the [
ON/OFF] button during
operation initiates Extra low operation.
Pressing the [
ON/OFF] button twice
within three seconds, or pressing and
holding it for
five
seconds, stops operation.
* When 24-hour Ventilation is set to on, “24HR VENTILATION” will be displayed
in the dot display during Extra low operation. The supply fan will stop and the
exhaust fan will perform low notch operation if the system enters cold region
intermittent mode during 24 hours operation.
* For the Lossnay models without those functions, those setting items will be
nondisplay.
[3] Mode selection
(1) Use of clock setting
To switch the setting, press the [
ON/OFF] button.
Dot display
Display
Function
Check
oFF
The clock function cannot be used.
on
The clock function can be used.
(Factory setting)
* Set to ON to enable Weekly timer and Night purge.
(3)
SA Temperature Display Setting
Set whether or not to display the SA temperature. Press the
[ ON/OFF]
button to switch between the following settings.
Dot display
Display
Check
oFF
SA
on
SA
*
*
The indicated temperature is the value of the Lossnay set as the main unit.
During By-pass operation, the SA temperature is not indicated even if display is set to on.
(4)
OA Temperature Display Setting
Set whether or not to display the OA temperature. Press the
[ ON/OFF]
button to switch between the following settings.
Dot display
Display
Check
oFF
OA
on
OA
* The indicated temperature is the measured OA intake temperature in the Lossnay
unit set as the main unit. The indicated OA temperature may differ from the actual
OA temperature.
(5)
RA Temperature Display Setting
Set whether or not to display the RA temperature. Press the
[ ON/OFF]
button to switch between the following settings.
Dot display
Display
Check
oFF
RA
on
RA
Temperature displayed
(factory setting)
Temperature not displayed
(6)
Exchange Efficiency Correction
Correct the exchange efficiency for calculating the SA temperature (calculated
value). Use the
[
G
CLOCK buttons Back]
to chage the value by -1%,
and use the
[
G
CLOCK buttons Ahead]
to change the value by +1%.
Dot display
Display
Function
Check
30~99
Factory setting: 70(%)
* The indicated temperature is the measured RA intake temperature in the Lossnay
unit set as the main unit. The indicated RA temperature may differ from the actual
RA temperature.
* During By-pass operation, the RA temperature is not indicated even if display is set to on.
* Setting range: 30 to 99%
(2) Timer function setting
Selects whether to use a Weekly timer, Simple timer, or not to use
any timer.
To switch the setting, press the [
ON/OFF] button.
Dot display
Function
Check
The weekly timer can be used. (Factory setting)
When the use of clock setting is OFF, the “WEEKLY
TIMER” cannot be used.
The simple timer can be used.
The timer mode cannot be used.
(3) Contact number setting for error situation
To switch the setting, press the [
ON/OFF] button.
Dot display
Function
Check
The set contact numbers are not displayed in case of
error. (Factory setting)
The set contact numbers are displayed in case of
error.
* Setting the contact numbers
To set the contact numbers, follow the following procedures.
Move the flashing cursor to set numbers. Press the OPERATION buttons to
move the cursor to the right (left). Press the [
CLOCK] buttons to set the
numbers.
Pressing the CLEAR button will clear the set number.
[4] Display change
(1) Filter cleaning setting
(SW5-5)
Set to OFF to disable Filter maintenance display.
To switch the setting, press the [
ON/OFF] button.
Dot display
Display Other indicators
Function
Check
on
With maintenance sign
(cumulative operation
time : 3000 hours)*
oFF
No maintenance sign
(Factory setting)
* For Extra low fan speed, half of the actual operation time is added to the normal
cumulative time.
(2) Lossnay cores cleaning setting
Set to on to enable Lossnay core maintenance display.
To switch the setting, press the [
ON/OFF] button.
Dot display
Display Other indicators
Function
Check
on
With maintenance sign
(cumulative operation
time: 6000 hours)*
oFF
No maintenance sign
(Factory setting)
* For Extra low fan speed, half of the actual operation time is added to the normal
cumulative time.
Other indicators
Function
Other indicators
Function
Other indicators
Function
Ventilation - tilstande Operation Section
*
1
The temperatures displayed on the remote controller are the temperatures
detected at the inlet port of the product main unit, and may differ from the actual
OA temperature and RA temperature.
Display(example)
[5]
How to Display the Temperature
Each press of the Return button switches between the display and non-display of the
OA/RA inlet temperature*
1
and heat-exchanged SA temperature (calculated value)*
2
.
(the temperature is not displayed when the temperature display setting is seto to OFF.)
(calc)
Temperature displayed
(factory setting)
Temperature not displayed
Temperature displayed
(factory setting)
Temperature not displayed