C-104

4

To register the interlocked operation of the Lossnay unit and the indoor unit.

Use the [TEST RUN] buttons (shown as 

D

) to register the interlock between the Lossnay indicated in “OA UNIT

ADDRESS NO.” and the indoor unit indicated in “INDOOR UNIT ADDRESS NO.”

5

To return to the normal operation mode.

Press and hold down both the [FILTER] button (shown as 

A

) and the “Louver” button (shown as 

B

) at the same time.

The function returns the unit to the normal operation mode. (OFF)

Note: 

Set the indoor unit to the smallest address number in a group followed by the Lossnay unit.  If this is not performed, the
Lossnay unit will not operate.

If there are multiple indoor units to be interlocked with the Lossnay unit, perform Steps 

3

and 

4

above for each.

15.3.4 Searching for interlocked registered units

6

Display the indoor unit address number at “OA UNIT ADDRESS NO.” 

Press the “Operation mode” button (shown as 

G

).

7

Use the

and

[TIMER SET] buttons (shown as 

H

) to select the address of the indoor unit to be registered. 

8

Press the “Timer/continuous” button (shown as 

E

) to alternate between the two displays.  

INDOOR UNIT
ADDRESS NO.

OA UNIT ADDRESS NO.

INDOOR UNIT
ADDRESS NO.

OA UNIT ADDRESS NO.

(Alternation)

When registration has been completed suc-
cessfully, the display alternates between the
two displays shown in the figure.

If there is an error in the registration, “

will flash to indicate the number of the unit.

INDOOR UNIT
ADDRESS NO.

OA UNIT ADDRESS NO.

INDOOR UNIT
ADDRESS NO.

OA UNIT ADDRESS NO.

INDOOR UNIT
ADDRESS NO.

OA UNIT ADDRESS NO.

INDOOR UNIT
ADDRESS NO.

OA UNIT ADDRESS NO.

(Alternation)

Address of the
registered unit

Press once again to return to “INDOOR UNIT ADDRESS NO.” shown in Step 

2

.

Содержание LGH-100RX5 -E

Страница 1: ...Lossnay Remote Controller ...

Страница 2: ......

Страница 3: ...1 to 15 Lossnay units together at the same time When using M NET transmission to operate from a centralized remote controller use the PZ 60DR E OR PZ 52SF E It can start and stop the unit change fan speed and switch the ventilation mode It also includes indicators that show errors and when filter maintenance is required Function is limited in case of LGH RX5 E Refer to page C 91 Lossnay M NET Remo...

Страница 4: ... from an external device used to operate Lossnay It is compatible with 12V 24V DC or uncharged a contact signal Switching High Low or Extra Low fan speed is available by external input CO2 sensor or other equipment is connected Switching By pass is available by external input Operation Mode Used for selecting enabling disabling of the on off control signal from an external device and for setting i...

Страница 5: ...n monitor change ON OFF ON OFF and external control priority ON OFF mode Weekly timer simple timer available for PZ 60DR E Delayed time can be varied only when the PZ 41SLB E is connected Automatic power recovery is fixed when PZ 60DR E or PZ 41SLB E is connected Function cannot be performed when PZ 41SLB E is con nected Uncharged a contact Remote display adaptor PAC SA88HA E is required Uncharged...

Страница 6: ...troller Outdoor unit Indoor unit MA remote controller Lossnay Indoor unit MA remote controller Lossnay Indoor unit Indoor unit MA remote controller Indoor unit MA remotecontroller Lossnay Indoor unit MA remote controller Indoor unit MA remote controller Lossnay Indoor unit Indoor unit Interlock Group 1 Interlock Group 5 Interlock Group 3 Interlock Group 4 Interlock Group 2 Outdoor unit Outdoor uni...

Страница 7: ...A C A C Air conditioning unit side remote controller Air conditioning unit side remote controller Air conditioning unit side remote controller Remote controller PZ 60DR E or PZ 41SLB E Indoor unit of air conditioner 01 Centralized controller 000 Outdoor unit 51 Operation settings MA remote controller Lossnay 02 Lossnay remote controller PZ 60DR E Group 1 Group 2 Use Lossnay remote controller PZ 60...

Страница 8: ...l remote controller Lossnay operation when indoor unit is stopped Lossnay stopping when indoor unit is operating Lossnay fan speed switching High Low Other common items Lossnay error indicator Ventilation mode Fixed to automatic Filter maintenance indicator Delayed operation External control operating mode selection Number of indoor units for interlocked group setting with one Lossnay unit One uni...

Страница 9: ...Z 60DR E LOSSNAY remote controller PZ 60DR E Mr Slim outdoor unit Mr Slim indoor unit M NET remote controller LOSSNAY RX5 LOSSNAY RX5 LOSSNAY RX5 LOSSNAY RX5 LOSSNAY remote controller PZ 60DR E LOSSNAY RX5 Ext signal source LOSSNAY remote controller PZ 60DR E Interlocked with City Multi indoor units Interlocked with Mr Slim indoor units LOSSNAY units only Interlocked with external devices Indoor u...

Страница 10: ...EST TEMP TIMER SET CLOCK ON OFF LIMIT TEMP Without Lossnay interlock switches and indicators Remote controllers for Mr Slim indoor unit PAR 21MAA PAR 21MAA ON OFF FILTER CHECK OPERATION CLEAR TEST TEMP MENU BACK DAY MONITOR SET CLOCK ON OFF ERROR CODE AFTER TIMER TIME SUN MON TUE WED THU FRI SAT ON OFF Hr AFTER FILTER FUNCTION ONLY1Hr WEEKLY SIMPLE AUTO OFF Remote controllers for Lossnay unit Loss...

Страница 11: ...y Power supply Non polar Two wires Remote controller PZ 60DR E or PZ 41SLB E 1 Connect from Lossnay Unit 1 to Lossnay Unit 2 and from Unit 2 to Unit 3 and so on up to a maximum of 15 units using a transmission cable PVC insulated PVC jacketed and either between 0 65 and 1 2 or between 0 3 mm2 and 1 25 mm2 in cross section 2 Change the setting on the main sub switch SW1 on the second and subsequent...

Страница 12: ...locations PZ 60DR E PZ 41SLB E remote controller switches are con The remote controller gives priority to the last touch nected Lossnay Power supply Lossnay Power supply Transmission cable extension is 500 m or less 0 65 to 1 2 PVC cable or 0 3 mm2 to 1 25 mm2 strand wire MAX 15 units Remote controller PZ 60DR E or PZ 41SLB E Transmission cable extension is 500 m or less 0 65 to 1 2 PVC cable or 0...

Страница 13: ...ch group Number of Lossnay units that can be set to interlocked oper ation with one indoor unit Operation of Lossnay unit only When indoor unit is stopped Independent Lossnay unit start and stop When indoor unit is operating Delayed operation Optional setting Switching fan speed Ventilation mode Filter indicator Error Restrictions and precautions Details One unit One unit Possible Not possible 30 ...

Страница 14: ...ote controller PZ 60DR E Lossnay remote controller PZ 60DR E Lossnay remote controller PZ 60DR E Lossnay remote controller PZ 60DR E Lossnay remote controller PZ 60DR E Centralized controller 000 Group 1 One Lossnay unit and one Lossnay remote controller Group 2 Without a Lossnay remote controller Group 3 Multiple Lossnay units and one Lossnay remote controller Group 4 One Lossnay unit and two Los...

Страница 15: ...r Outdoor unit 059 Centralized controller 000 Group 1 One Lossnay unit and one Lossnay M NET remote controller Group 2 Without a Lossnay M NET remote controller Group 3 Multiple Lossnay units and one Lossnay M NET remote controller Group 4 One Lossnay unit and two Lossnay M NET remote controllers Group 5 Multiple Lossnay units and two Lossnay M NET remote controllers Group 6 One Lossnay unit is in...

Страница 16: ...2SF E Refer to page C 92 For details about the operation and display of the centralized controller AG 150A Refer to page C 93 No of controllable Groups Units Model Local Remote MELANS Series Start Stop Switching air volume Switching Ventilation mode Priority instructions to local remote controller Local permitted Status Operation Stop Switching air volume Ventilation mode Error Error information F...

Страница 17: ...troller PZ 41SLB E cannot be used with any group in this application Multiple Refrigerant Systems Group1 Lossnay 004 Group3 Lossnay 008 Lossnay 002 Indoor unit 001 MA Remote controller Group2 Indoor unit 003 Indoor unit 005 Indoor unit 007 MA Remote controller Indoor unit 006 MA Remote controller Outdoor unit 051 Outdoor unit 055 address Refrigerant 1 Refrigerant 2 Group 1 One Lossnay unit is inte...

Страница 18: ...set a schedule for the year and a weekly schedule for individual seasons For details about the operation or display of the remote controller PAR F27MEA PAR 21MAA please refer to the specific remote controller manuals No of controllable Groups G Units Model Local Remote MELANS Series Start Stop Switching air volume Switching ventilation mode Prohibit Local Status Operation Stop Switching air volume...

Страница 19: ...tion is possible with indoor unit remote controller In this case operation can switch between High Low Off It is possible to switch Lossnay operation only between High Low Off with the indoor unit remote controller It is possible to controll the Lossnay unit from Lossnay remote controller PZ 60DR E More additional function such as Extra Low fan speed is available 2 When two or more indoor units in...

Страница 20: ... controller 000 Lossnay remote controller PZ 60DR E Lossnay remote controller PZ 60DR E Lossnay remote controller PZ 60DR E Lossnay remote controller PZ 60DR E Lossnay remote controller PZ 60DR E Lossnay remote controller PZ 60DR E Lossnay remote controller PZ 60DR E Group 1 One Lossnay unit and one Lossnay remote controller Group 2 Without Lossnay remote controller Group 3 Multiple Lossnay units ...

Страница 21: ...tions and functions of the LON adaptor refer to the materials regarding the LONWORKS compatible adaptor Table of Functions System Example Using M NET Lossnay Lossnay Building management system LMAP02 E Lossnay remote controller PZ 60DR E Lossnay remote controller PZ 60DR E M NET LONWORKS M NET Lossnay Lossnay LMAP02 E Lossnay remote controller PZ 60DR E Lossnay remote controller PZ 60DR E Connect ...

Страница 22: ...alfunction uncharged a contact signal output Contactor rating Max 240V AC 1A 24V DC 1A Min 220V AC 100mA 5V DC 100mA Output terminal during Lossnay unit malfunction uncharged a contact signal output Output delay function 2 is possible by DIP switch 5 6 Contactor rating Max 240V AC 1A 24V DC 1A Min 220V AC 100mA 5V DC 100mA Input connector for switching By pass Establish the wire connection by inse...

Страница 23: ...ed Operating condition Operating Stopped External signal Remote controller ON OFF button pressed Operating condition Operating Stopped External signal Remote controller ON OFF button pressed Operating condition External signal Remote controller ON OFF button pressed Operating condition External signal Remote controller ON OFF button pressed Operating condition Operating Stopped Operating Stopped E...

Страница 24: ...ts operat ing Refer to page C 74 5 3 Multiple External Device Operation PZ 60DR E PZ 41SLB E M NET System Example When the Operation Signal is a Uncharged a contact Level Signal When there are multiple air conditioners or other external devices Characteristics Ordered parts Notes Lossnay operates at the same time as any of the external devices Remote controller Can receive level signal uncharged a...

Страница 25: ...mote display output for the indoor unit and the external control input for the Lossnay unit Note Do not make the setting of the indoor and Lossnay units to be interlocked because the ventilation switch on the MA remote controller will become invalid and the error indicator for the Lossnay unit will appear only on the Lossnay remote controller Lossnay remote controller PZ 60DR E Indoor unit M NET t...

Страница 26: ...rinted circuit board Within 500 m CN2L Mr Slim Indoor unit White Lossnay External control input TM2 0 5 mm2 to 1 mm2 sheathed PVC cable External device 12 or 24 VDC Overall connection extension length Follow the operation manual for the external equipment 123 2 When the external device has a charged operating signal of 12 VDC or 24 VDC Refer to page C 68 Connect the interlocking cable connector si...

Страница 27: ...ut TM2 Lossnay 4 Multiple uncharged a contacts Connect the power supply cable from the Electrically operat ed damper to 9 and 0 of the monitor output terminal block TM4 with reference to the wire connection diagram Operation monitor output with delay function 1 can be possi ble Refer to function setting 6 refer to C 74 Setting for TM4 9 0 Note Don t tighten screws of terminal block with a torque l...

Страница 28: ... controller TM1 Switch Power source for LOSSNAY TM2 Lossnay 1 2 3 SW1 CN16 SW1 Low fan speed operation switch When closed For Low fan speed operation Brown 1 Red 2 Orange 3 Yellow 4 Green 5 Not used Insulate completely Max wiring length 10 m Fan speed Ventilation mode selection CO2 sensor etc When CO2 increases Closed Remote display adaptor Optional PAC SA88HA E Lossnay control board When SW1 is O...

Страница 29: ...ain It is not necessary to connect to any Lossnay with the Sub setting Connect any sensor etc with the external change input to the Lossnay unit set to Main Any Lossnay with the Sub setting will operate at the same High Low setting as the Lossnay with the Main setting when there is sensor signal input Lossnay Main Lossnay Sub Lossnay Sub Main Sub Sub CO2 sensor PZ 60DR E or PZ 41SLB E Note When us...

Страница 30: ...unit Limit the total length of transmission wires no longer than 500 m Limit the wiring length between Lossnay and the power supply unit Optional or the outdoor unit no longer than 200 m One shielded wire is connected to TB5 S on the PCB on terminal Address setting is required Refer to function setting section M NET transmission cable Connect any of the City Multi indoor unit or Mitsubishi Electri...

Страница 31: ...tralized controller transmission cable Indoor unit transmission cable Outdoor unit Indoor unit of air conditioner Lossnay Lossnay TB7 TB3 MA remote controller Lossnay remote controller PZ 60DR E Power supply unit PAC SC51KUA M NET 24 VDC Centralized controller AG 150A Power supply unit PAC SC50KUA Lossnay M NET remote controller PZ 52SF E Lossnay M NET remote controller PZ 52SF E Lossnay Lossnay L...

Страница 32: ...ead of PZ 60DR E However connecting point is different Power consumption of each central controller Number of conversion as Lossnay remote controller Model Two units Four units Two units System remote controller ON OFF remote controller PAC SF44SRA PAC YT40ANRA PAC YT34STA Schedule timer Two units Centralized controller G 50A Two units AG 150A Centralized controller Twelve units GB 50A ...

Страница 33: ...llers Lossnay M NET remote controllers 32 2 1 MA remote controllers and Lossnay units are not counted 2 The number of units varies depending on the functions of the indoor units and outdoor units For details refer to the docu mentation for CityMulti Power supply unit M MET Centralized controller AG 150A Lossnay M NET remote controller PZ 52SF E ME remote controller ME remote controller Indoor unit...

Страница 34: ...t will result in signal error and cause the system not to operate properly OK Outdoor unit System one System two Indoor unit of air conditioner Indoor unit of air conditioner Two core cable 5cm or more Two core cable Multi core cable Lossnay Lossnay Lossnay Lossnay Outdoor unit Outdoor unit Outdoor unit Lossnay M NET remote controller PZ 52SF E Lossnay M NET remote controller PZ 52SF E Air conditi...

Страница 35: ... mm2 Maximum length from an end to the other end Less than 200m 2 Remote controller Type of cables ME remote controller Lossnay remote controller MA remote controller Two core shielded cable MVVS Diameter 0 5 0 75mm2 0 75mm2 1 25mm2 0 3 1 25mm2 Note Use 1 25 2 0mm2 cables for the portion of exceeding 10m and apply the rule of 7 3 Length of Control Cable on the next page 200m Max ...

Страница 36: ...Centralized remote controller L4 T B 2 T B 3 Lossnay M NET remote controller PZ 52SF E Lossnay M NET remote controller PZ 52SF E Outdoor unit Indoor unit Lossnay Lossnay Lossnay Lossnay L2 L1 L3 Air conditioner M NET remote controller Ground Transmission booster T B 2 T B 3 L3 L5 Notes Always install the ground cable for the transmission cables by routing the central control system through the pow...

Страница 37: ...7 6 5 4 3 2 1 0 10 2 Fixed 1 9 8 7 6 5 4 3 2 1 Use the smallest address within the same group of indoor units Make the address of the indoor units connected to the sub BC controller larger than the address of indoor units connected to the main BC controller The smallest address of indoor unit in same refriger ant system 50 The address automatically becomes 100 if it is set as 01 to 50 The address ...

Страница 38: ...ddress ME remote controller ME remote controller Lossnay M NET remote controller PZ 52SF E Lossnay M NET remote controller PZ 52SF E Lossnay M NET remote controller PZ 52SF E K control remote controller K control remote controller K control remote controller K control remote controller Mr Slim A control remote controller M NET compatible A control Mr Slim outdoor unit A control Mr Slim indoor unit...

Страница 39: ...oller address is not registered H0 is displayed and the system does not start up 7 No more than three Lossnay remote controllers can be set to the same group in a system using a System Con troller Precautions 1 The maximum number of indoor units of air conditioner that can be interlocked is 16 Refer to page C 18 2 One Lossnay can be interlocked with an indoor unit of air conditioner Refer to page ...

Страница 40: ...s where the temperature has risen due to office equipment use Only when interlocked with City Multi and Mr Slim indoor unit 9 2 Ventilation mode control Lossnay heat exchange ventilation or bypass normal ventilation is achieved by switching the air duct inside the Lossnay unit with a damper 1 Ventilation mode There are 3 control modes Lossnay ventilation heat exchange ventilation mode Heat exchang...

Страница 41: ...oller PZ 41SLB E The Function selector button of the remote controller permits ventilation mode switching for automatic Loss nay and bypass ventilation A control remote controller K control remote controller Remote controller connection prohibited with Lossnay Fixed to automatic ventilation System interlocked with Mr Slim None Level signal pulse signal output device and external device only Remote...

Страница 42: ...ture of the air conditioner remote controller Note that the b map will be followed while Mr Slim and City Multi indoor units are stopped Cooling mode Winter 0 5 10 15 20 25 30 35 40 0 5 10 15 20 25 30 35 40 Indoor temperature ºC Heating mode Summer 0 5 10 15 20 25 30 35 40 0 5 10 15 20 25 30 35 40 Indoor temperature ºC Remote controller Set temperature Bypass ventilation Prohibition temperature 8º...

Страница 43: ...r temperature ºC Undetermined area When operation starts under this condition Lossnay ventilation will be activated When this condition is reached after operation starts the current ventilation mode is maintained Lossnay ventilation area Bypass ventilation area Undetermined area Bypass Ventilation Bypass Ventilation Undetermined area 6 Ventilation mode change recommendation RECOMMENDED VENTILATION...

Страница 44: ...n two to three times before starting repairs If it is thought that there is a printed circuit board malfunction check for disconnected wires in the print pattern burnt parts or discoloration If the printed circuit board is replaced make sure that the switch settings on the new board are the same as the old board Part names used in the following text correspond to those listed in the parts catalog ...

Страница 45: ... A B 7 Is the wiring length of the transmission cable within the regulations Basic system PZ 60DR E PZ 41SLB E Total extension within 500 m M NET control Maximum extension within 200 m total extension within 500 m Action Use specified cables Wire the transmission cable at least 5 cm away from the power supply cable Wire the transmission cables away from the signal cables Using suitable cables wire...

Страница 46: ...ith level signal pulse signal output devices and Mr Slim units 8 Do the external signals meet specifications Level signal Charged 12 V DC 24 V DC uncharged a contact Pulse signal Charged 12 V DC 24 V DC uncharged a contact A pulse width of 200 ms or greater is required Input a signal that suits the specifi cations 9 Are the type of input signal and the setting of the pulse input matched Pulse sign...

Страница 47: ...supply fan operation monitor mal function monitor bypass operation monitor and operation monitor with delay function 8 When using the operation monitor is the setting of the output signal cor rect When using PZ 60DR E Check the operation monitor setting from the function selection Refer to page C 70 When not using PZ 60DR E Check the setting of the operation monitor SW5 2 on the Lossnay cir cuit b...

Страница 48: ...ength of the trans mission cable wiring Using suitable cables wire the transmission cables so that they are separated from one another Use the same type of remote controller 3 Interlock operation with external device does not occur Is the specified power being supplied to the Lossnay unit Are the signal cables from the external devices wired according to regulations The type of external signal doe...

Страница 49: ...le 1 2 2 Check the Lossnay address and set for an address corresponding to interlock operation Check the length of the trans mission cable wiring Refer to page C 36 Change to the PZ 60DR E or PZ 52SF E remote controller PZ 41SLB E cannot be used with the M NET 1 No Lossnay does not inter lock with City Multi indoor unit Lossnay cannot be operated by the ventila tion button on the ME remote control...

Страница 50: ...en power is supplied to the system the display of PZ 52SF E goes blank and the system does not start The restricted number of connected PZ 52SF E units have been exceeded The length of the transmission cable wiring is longer than specified longer than maximum 200 m from the power supply unit longer than 500 m between ends Check the restricted number of remote controller units when using the power ...

Страница 51: ...y PZ 52SF E Lossnay address setting SA1 SA2 is wrong Lossnay address setting SA1 SA2 was changed The transmission cable power supply restric tions have been exceeded Group setting has not been performed after replacement of the circuit board 9 LC 6608 appears on the remote controller and the Lossnay does not operate PZ 60DR E is connected to the terminal block TB5 A B for the M NET transmission ca...

Страница 52: ...heck the transmission cable connection Check the length of the transmission cable wiring Error Cause Action RC6608 SRC 6608 Communica tion error between remote con trollers when two remote con trollers are connected Multiple transmission cables are wired using multi core cables Transmission cable and power sup ply cable are too close Transmission cable is not securely connected The length of the t...

Страница 53: ... is longer than specified longer than 500 m Turn off the main power and set the Main Sub selection switch SW1 Set the first unit to Main and the second and following units to Sub Using suitable cables wire the transmission cables so that they are separated from one another Wire the transmission cable at least 5 cm away from the power supply cable Check the transmission cable connection Check the l...

Страница 54: ...s When external devices are not con nected check the TM3 6 7 output setting switch SW5 6 Refer to page C 75 3602 3 blinks Damper related error Damper board operation is not cor rect Connectors for the damper unit are not correctly connected The switch SW5 10 setting is incorrect Remove the rod and check whether the damper board can be moved manually Check the connection of the lead wire connectors...

Страница 55: ...to Sub Using suitable cables wire the transmission cables so that they are separated from one another Wire the transmission cable at least 5 cm away from the power supply cable Check the transmission cable connection Check the length of the transmission cable wiring CLEANING FILTER blinking Filtercleaningwarn ingaccordingtototal hoursofoperation It is time to clean the Lossnay air fil ter After cl...

Страница 56: ...de set ting Refer to page C 76 Check the remote local switching CN32 Refer to page C 71 6 Cannot switch fan speed with the remote con troller High Low Extra Low fan speed switching exter nal input CN16 is ON When using PZ 60DR E POWER VENT START is set to on with the function selec tion of the remote controller When not using PZ 60DR E the function selection switch for Power supply exhaust when op...

Страница 57: ...m the resultant operation will not be in accordance with the setting Perform the timer setting with one remote controller only and use the other remote controller as Timer off indicator Error Cause Action 10 The fan does not stop even though the remote controller is set to stop Operation monitor with delay function is set to ON Function selection switch SW2 8 or SW5 6 is set to ON Check the functi...

Страница 58: ...SF E or MELANS Power is not supplied to Lossnay Power that does not follow specifications is used Transmission cable to the Lossnay is not con nected Transmission cable is connected to the wrong terminal of the Lossnay unit Lossnay address was changed The length of the transmission cable wiring is longer than specified longer than maximum extension 200 m longer than 500 m between ends Check the po...

Страница 59: ...nger than 500 m The Delay operation is set with the function selection of PZ 60DR E or PZ 41SLB E or the function selection switch SW5 1 on the Lossnay circuit board The ON Interlocked or OFF Interlocked is set with the function selection of PZ 60DR E or PZ 41SLB E or the function selection switches SW5 7 SW5 8 on the Lossnay circuit board When using multiple Lossnay units the exter nal control in...

Страница 60: ...n setting for air conditioner defrost ing with the PZ 60DR E function selection or the function selec tion switch SW5 3 Refer to page C 75 and C 90 7 Fan speed will not change High Low Extra Low fan speed switching exter nal input CN16 is ON When using PZ 60DR E POWER VENT START is set to on with the function selec tion of the remote controller When not using PZ 60DR E the function selection switc...

Страница 61: ...or out put setting with the PZ 60DR E function selection or the function selection switch SW5 2 on the Lossnay circuit board Refer to page C 72 and C 90 11 Night purge operation does not work even though Night purge oper ation is set The night purge conditions have not been sat isfied Lossnay has been started or stopped during the display of Night purge Night purge operation will not be performed ...

Страница 62: ...f PZ 60DR E or when returning to the normal display from the function selection mode or the maintenance mode Button operations may not be accepted immediately depending on communication processing When an operation has not been accepted perform the operation after several sec onds have passed 7 24 HR VENTILATION is not displayed on the PZ 60DR E function selection This is not displayed because the...

Страница 63: ... the following circumstances The night purge conditions have not been satisfied Lossnay has been started or stopped during the display of Night purge Night purge operation will not be performed when CENTRAL is displayed 17 Damper board does not oper ate When switching the ventilation mode with the remote controller a maximum delay of 30 seconds will be generated depending on the timing 18 Delay op...

Страница 64: ...lation to meet local electrical regulations Always use double insulated PVC cable for the transmission cables Wiring work must be performed by qualified professionals All supply circuits must be disconnected before obtaining access to the terminal devices 11 1 1 Names of components in control box LGH 15 to 100 RX5 TM1 LED1 LED4 LED2 SW1 SW2 SW5 SA1 SA2 TM4 TB5 TM2 TM3 11 1 2 Wire connection diagra...

Страница 65: ... x201 x202 x203 x101 x102 x103 M M M 1 2 1 M2 EXHAUST SUPPLY EXHAUST FAN MOTOR FAN MOTOR FAN MOTOR SUPPLY FAN MOTOR C C C C cable transmission M NET MELANS non polar Mr Slim output 7 8 Malfunction monitor monitor output 6 7 By pass or Delay2 Sheild Wire 12V or 24V DC BROWN RED TM4 CN16 10 8 7 6 1 2 3 CN5 1 2 9 A B S X10 CN32 X11 X12 Isolator TAB2 TAB1 CN9 CN10 TAB5 TAB3 TM3 TB5 Transmission cable ...

Страница 66: ...s The following system configuration can be created Connect the necessary parts 1 When connecting with remote controller PZ 60DR E PZ 41SLB E 2 When interlocked with indoor unit of air conditioner or other external device including other manufactures 3 When interlocking with a pulse output device 4 When operating multiple Lossnay units 5 When take malfunction monitor output or take By pass operati...

Страница 67: ...l block with a torque larger than 0 5 Nm It could damage the PCB 2 Confirm that the pulse input switch SW2 2 is set to OFF Set to OFF at time of shipment Operating switch for external device Power supply External device Lossnay Power supply Remote controller PZ 60DR E or PZ 41SLB E 1 When connecting with remote controller PZ 60DR E PZ 41SLB E 2 When interlocked with indoor unit of air conditioner ...

Страница 68: ...PZ 60DR E or PZ 41SLB E Connect to remote controller PZ 60DR E or PZ 41SLB E Lossnay Sub MAX 15 units Power supply Lossnay Sub Power supply Power supply Connect to third Lossnay Main Sub 2 1 2 1 Transmission cable First Lossnay Second Lossnay TM4 Factory setting main TM4 2 Multiple Lossnay units connection Connect from Lossnay unit 1 First Lossnay unit to Lossnay unit 2 and from unit 2 to unit 3 a...

Страница 69: ...pulse signal can be connected to the external device of the main Lossnay only Connect the power to each respective Lossnay unit When the LGH 150RX5 and LGH 200RX5 types are connected they operate at low fan speed even if extra low fan speed is selected 1 2 SW2 3 4 5 6 7 8 9 10 ON ON OFF Lossnay Main Power supply External device Operating switch for external device Remote controller PZ 60DR E or PZ...

Страница 70: ...en CO2 increases Closed SW1 High fan speed operation switch When closed For High fan speed operation Remote display adaptor Optional PAC SA88HA E Brown 1 Red 2 Orange 3 Yellow 4 Green 5 Not used Insulate completely Max wiring length 10 m Lossnay control board Fan speed Ventilation mode selection CO2 sensor etc When CO dec 2 increases Closed Remote display adaptor Optional PAC SA88HA E Lossnay cont...

Страница 71: ...ON OFF adaptor Optional PAC SA88HA E Lossnay control board CN32 SW1 SW2 Y X Y X Remote control board Max wiring length 10 m Relay circuit Orange 1 Red 2 Brown 3 Relay power supply S B A TB5 M NET transmission cable Shielded wire M NET transmission cable input terminal block 9 When using the remote local switching and the ON OFF input level signal The remoto controller PZ 41SLB E cannot be used Ins...

Страница 72: ...y exhaust when operation starts SA fan fixed at Low speed EA fan fixed at Low speed Power supply ON OFF Bypass ventilation priority at Automatic mode Setting for TM4 9 10 output Supply Extra High High Exhaust Extra High High Delay setting Operation monitor output Auto restoration after power failure Filter maintenance indication setting Setting for TM3 6 7 output Interlock mode setting Exhaust fan...

Страница 73: ... Switching to power supply exhaust when operation starts This sets the fan to run forcibly for 30 minutes when operation starts to ventilate the indoor area After 30 minutes the sys tem switches to enable fan speed adjustment from the remote controller Use this setting if the indoor air is contaminated at night when the system is shut down and you desire to ventilate the indoor area quickly when o...

Страница 74: ...esponds to operation mode output TM490 based on SW5 2 setting factory setting Operation monitor output with delay function 1 Corresponds to operation mode output TM490 supply fan with following function Starts the output TM490 10 seconds after supply fan operates Lossnay continues to operate for 3minutes after stopping the output TM490 Caution Fan may be operating after turn off the switch of the ...

Страница 75: ...ER display on remote controller factory setting 3000 hours CAUTION When the setting for the cumulative operation time of the Lossnay is exceeded the filter cleaning display will appear on the indoor unit remote controller or the Lossnay remote controller After cleaning the filter the filter cleaning display can be reset Refer to the operating instructions for the remote controller OFF ON Operation...

Страница 76: ...nnected then test the system s operation referring to the operation manual for the remote controller 11 5 1 Trial operation using the remote controllers PZ 60DR E PZ 41SLB E and PZ 52SF E Follow the procedure shown in the operation manual for the remote controller the functions below 1 Start operation 2 Fan speed selection 3 Function selection 4 Stop operation 15 Exhaust fan stop at outdoor air lo...

Страница 77: ...a power supply unit and that the power has been turned on On systems with only a Lossnay a power supply unit is required Check if the pulse input switch SW2 2 is off Can be set from PZ 60DR E Check the overall cable length between the indoor unit or external device and Lossnay Refer to technical publication or other such documents Check the connections at the external control input terminal block ...

Страница 78: ...er Extra Low Low High Extra High Extra Low Low High Extra High Power On indicator Indicates that the power is on ERROR CODE indicator Displayed together with the malfunctioning unit 3 digits and an error code 4 digits Ventilation tilstande Indicates the ventilation mode status Heat exchange By pass Automatic Heat ex By pass or Operation Section MENU button MONITOR SET button BACK button Back Ahead...

Страница 79: ...the display to the standard control screen where 1 will now show the newly set day and time To change the time or day of the week start from Step 1 above Note If you are using two remote controllers setting the time and day of the week in one remote controller will cause the new setting to be applied to the other as well Operation Relevant button Relevant display items Sequence 1 Starting the Loss...

Страница 80: ...e operation to be carried out at the same time every day Example Operation 2 above which is the same for all days of the week Operation 1 settings for Sunday Start the Lossnay unit at 9 00 with fan speed set to High Operation 2 settings for every day Turn off the Lossnay unit at 10 00 How to Set the Weekly Timer 1 Be sure that you are at a standard control screen and that the weekly timer indicato...

Страница 81: ...screen even if the clock use setting is ON use clock 4 2 1 3 How to Set the Simple Timer 1 Be sure that you are at a standard control screen and that the simple timer indicator is visible in the display at 1 When something other than the Simple Timer is displayed set it to SIMPLE TIMER using the function selection of remote controller refer to section Installation Manual 5 Function selection 3 Mod...

Страница 82: ... it Example 2 Start the timer with OFF time is sooner than ON time ON Setting 5 hours OFF Setting 2 hours At 3 hours after timer start At 2 hours after timer start At Timer Start At 5 hours after timer start Display shows the timer s OFF setting hours remaining to OFF Display changes to show the timer s ON setting hours remaining to ON The time displayed is ON setting 5 hours OFF setting 2 hours 3...

Страница 83: ...is prohibited by the centralized controller ON OFF including timer operation Note May also be individually restricted When interlocked with external device The Lossnay unit can be started and stopped by external equipment 1 2 12 4 Care and Maintenance The contact telephone number will be displayed if CALL has been set Pressing the CLEAR button once will display the contact telephone number even wh...

Страница 84: ...lots and move the screwdriver in the arrow direction CAUTION Remove the cover carefully so as to avoid any damage Do not turn the screwdriver in the slot Doing so may damage the slot 4 Install the lower case on the switch box or directly on the wall When using the switch box When installing directly on the wall CAUTION Do not tighten the screws too tight Doing so may deform or crack the lower cove...

Страница 85: ...splay the NOT AVAILABLE message 2 If set to 24 hour Ventilation pressing the ON OFF button will cause this to be displayed in the dot display 24HR VENTILATION and the operation will switch to Extra low fan speed mode To stop operation press the ON OFF button twice within 3 seconds or press and hold the ON OFF button for 5 seconds If error code is displayed refer to the following table Error code C...

Страница 86: ...ction and Multi Ventilation modes 3 Power supply exhaust when operation starts POWER VENT START SW2 3 5 Switching to power supply exhaust when operation starts 4 Subordinate Lossnay settings 4 SUB SET Enable disable subordinate Lossnay unit supply and exhaust fan speed settings 5 Power supply ON OFF AUTO RECOVERY SETTING SW2 6 5 SW5 4 5 Controls stop and start operation by turning the power supply...

Страница 87: ...N buttons Back D Function selector butto Temperature display calc n C ON OFF DAY button G CLOCK buttons Back Ahead B MENU MONITOR SET button A BACK button A C Select from item1 Hold down the A button and press the C button for 2 seconds Hold down the A button and press the C button for 2 seconds 2 A C 3 B 4 B 5 C 6 A C or L A 1 Stop the Lossnay to start remote controller function selection mode 2 ...

Страница 88: ...See 6 2 See 6 3 See 6 4 Interlock mode setting INTERLOCK MODE Press the B button Pulse input setting INPUT SIGNAL Delayed operation settings DELAY OPERATION Exhaust operation settings for air conditioner defrosting EA SETTING DEFROST Hold down the A button and press the C button for 2 seconds or L button NOTE To return to the normal display hold down the A button and press the C button for 2 secon...

Страница 89: ...ing settings Dot display Display Check oFF RA on RA Temperature displayed factory setting Temperature not displayed 6 Exchange Efficiency Correction Correct the exchange efficiency for calculating the SA temperature calculated value Use the G CLOCK buttons Back to chage the value by 1 and use the G CLOCK buttons Ahead to change the value by 1 Dot display Display Function Check 30 99 Factory settin...

Страница 90: ...the summer to automatically ventilate a room at night while the air conditioner is stopped to discharge accumulated heat and thereby reduce the air conditioning load the next morning Enables or disables Night purge operation To switch the setting press the ON OFF button Dot display Display Function Check oFF Night purge mode is inactive Factory setting on Night purge mode is active See page 14 of ...

Страница 91: ...dicates the ventilation mode status Energy recovery Heat exchange HEAT EX Bypass BY PASS Automatic Heat ex Bypass Power Display Displayed while the Lossnay remote controller is on CHECK Display Displayed together with the malfunctioning unit three digits and an error code four digits Delay time Display Displays delay time Delay setting SETTING XX MIN DELAYED XX 0 60 During delay operation XX MIN D...

Страница 92: ...isplay flashes simultaneously with the display of the unavailable function ON OFF Button Switches between start and stop The lamp on the button stays lit during operation Fan Speed Adjustment Button Used to select the fan speed of either Low or High FILTER Button Press two times to reset the filter display HEAT EX BY PASS AUTO Low High INTERLOCKED Display Displayed when the Lossnay unit starts ope...

Страница 93: ...C 93 15 Appendix 15 1 Centralized Controller AG 150A For details on other function settings refer to the manual for the AG 150A ...

Страница 94: ...C 94 ...

Страница 95: ...C 95 5 ...

Страница 96: ...C 96 ...

Страница 97: ...C 97 ...

Страница 98: ...C 98 5 3 ...

Страница 99: ...C 99 ...

Страница 100: ... with a ventilation unit When changing Lossnay fan speed Press the Ventilation button C PAR 21MAA ON OFF FILTER CHECK OPERATION CLEAR TEST TEMP MENU BACK DAY MONITOR SET CLOCK ON OFF ERROR CODE AFTER TIMER TIME SUN MON TUE WED THU FRI SAT ON OFF Hr AFTER FILTER FUNCTION ONLY1Hr WEEKLY SIMPLE AUTO OFF Ventilation Display Displayed during ventilation Lossnay operation B A C Lossnay fan speed Low Los...

Страница 101: ...101 0 0 0 1 1 2 2 3 3 3 4 4 4 5 5 5 0 0 0 0 0 0 0 0 6 1 7 8 9 9 6 6 1 0 2 6 6 6 8 A 1 2 3 4 6 7 0 5 6 0 8 B B C A B C 9 A B C E 8 E D F G 1 1 2 0 D B D D 7 7 D F E G C D I A B H 15 2 2 Function Selection ...

Страница 102: ...e number display When registered via the Mode selection button the registered indoor unit begins fan operation When you want to know the location of the indoor units of the unit address number whose functions were sele cted check here When the unit address number is 00 or AL all the indoor units of the selected refrigerant address perform the fan operation Ex When refrigerant address 00 unit addre...

Страница 103: ...roller PAR F27MEA INDOOR UNIT ADDRESS NO INDOOR UNIT ADDRESS NO OA UNIT ADDRESS NO INDOOR UNIT ADDRESS NO OA UNIT ADDRESS NO Both INDOOR UNIT ADDRESS NO and OA UNIT ADDRESS NO will appear simultaneously E A B D H G C F PAR F27MEA ON OFF CENTRALLY CONTROLLED DAILY AUTO OFF REMAINDER ERROR CODE CLOCK ON OFF CHECK MODE FILTER TEST RUN 1Hr NOT AVAILABLE STAND BY DEFROST FILTER CHECK TEST TEMP TIMER SE...

Страница 104: ...each 15 3 4 Searching for interlocked registered units 6 Display the indoor unit address number at OA UNIT ADDRESS NO Press the Operation mode button shown as G 7 Use the and TIMER SET buttons shown as H to select the address of the indoor unit to be registered 8 Press the Timer continuous button shown as E to alternate between the two displays INDOOR UNIT ADDRESS NO OA UNIT ADDRESS NO INDOOR UNIT...

Страница 105: ...h are displayed according to their address number with the indoor unit If there is a transmission error the properties will flash as Check the wiring and the address then perform step A again B To return to the normal operation mode Press and hold down the FILTER button shown as A and the Louver button shown as B simultaneously to return the unit to the normal operation mode OFF INDOOR UNIT ADDRES...

Страница 106: ...Y08 004 Jan 2009 MEE ...

Страница 107: ...nks Model Number LGH 80RX5 E LGH 80RX5 E Specification LGH RX5 Controls Service Manual LGH RX5 Declaration of Conformity LGH RX5 Hand Book LGH RX5 Operation Manual Ventilation Brochure LGH RX5 Installation Manual ...

Отзывы: