C-104
4
To register the interlocked operation of the Lossnay unit and the indoor unit.
•
Use the [TEST RUN] buttons (shown as
D
) to register the interlock between the Lossnay indicated in “OA UNIT
ADDRESS NO.” and the indoor unit indicated in “INDOOR UNIT ADDRESS NO.”
5
To return to the normal operation mode.
•
Press and hold down both the [FILTER] button (shown as
A
) and the “Louver” button (shown as
B
) at the same time.
The function returns the unit to the normal operation mode. (OFF)
Note:
●
Set the indoor unit to the smallest address number in a group followed by the Lossnay unit. If this is not performed, the
Lossnay unit will not operate.
●
If there are multiple indoor units to be interlocked with the Lossnay unit, perform Steps
3
and
4
above for each.
15.3.4 Searching for interlocked registered units
6
Display the indoor unit address number at “OA UNIT ADDRESS NO.”
•
Press the “Operation mode” button (shown as
G
).
7
Use the
and
[TIMER SET] buttons (shown as
H
) to select the address of the indoor unit to be registered.
8
Press the “Timer/continuous” button (shown as
E
) to alternate between the two displays.
INDOOR UNIT
ADDRESS NO.
OA UNIT ADDRESS NO.
INDOOR UNIT
ADDRESS NO.
OA UNIT ADDRESS NO.
(Alternation)
•
When registration has been completed suc-
cessfully, the display alternates between the
two displays shown in the figure.
•
If there is an error in the registration, “
”
will flash to indicate the number of the unit.
INDOOR UNIT
ADDRESS NO.
OA UNIT ADDRESS NO.
INDOOR UNIT
ADDRESS NO.
OA UNIT ADDRESS NO.
INDOOR UNIT
ADDRESS NO.
OA UNIT ADDRESS NO.
INDOOR UNIT
ADDRESS NO.
OA UNIT ADDRESS NO.
(Alternation)
Address of the
registered unit
Press once again to return to “INDOOR UNIT ADDRESS NO.” shown in Step