Checklist for PZ-60DR-E or PZ-41SLB-E (Table 3-1)
1
No.
Nothing displays on the
LCD.
«
Transmission cable is connected to the wrong
terminal block.
«
No Lossnay unit is set to “Main”.
«
Power is not supplied to Lossnay.
«
Power that does not follow specifications is
used.
«
Transmission cable is not securely connected.
«
The length of the transmission cable wiring is
longer than specified (longer than 500 m).
«
Check the transmission cable con-
nection. (TM4
1
,
2
for the transmis-
sion cable from the remote controller)
«
Turn off the main power supply and
set the Main/Sub selection switch
(SW1) (first unit to “Main”, and sec-
ond and following units to “Sub”).
«
Check the power supply to Lossnay.
«
Check the power supply.
«
Check the transmission cable connection.
«
Check the length of the trans-
mission cable wiring.
2
Starts or stops, or the
display changes, by
itself.
«
Multiple transmission cables are wired using
multi core cables.
«
Transmission cable and power supply cable
are too close.
«
Using suitable cables, wire the
transmission cables so that they
are separated from one another.
«
Wire the transmission cable at least 5
cm away from the power supply cable.
3
Displays an error code
that is not in the check
list.
«
Liquid crystal display characters on the remote
controller are missing.
«
Poor return action of the remote controller buttons.
«
Replace the remote controller.
«
Replace the remote controller.
4
Cannot stop the Lossnay
with the remote controller.
(“CENTRAL” is displayed)
«
Operation of the remote controller has been
prohibited by MELANS.
«
“INTERLOCK MODE” is set to “oUT” (external
input given priority).
«
Remote/local switching (CN32) is set to
“Remote.”
«
Check the setting of the
MELANS.
«
Check the interlock mode set-
ting. (Refer to page C-76)
«
Check the remote/local switching
(CN32). (Refer to page C-71)
6
Cannot switch fan speed
with the remote con-
troller.
«
High/Low/Extra Low fan speed switching exter-
nal input (CN16) is ON.
«
When using PZ-60DR-E, “POWER VENT
START” is set to “on” with the function selec-
tion of the remote controller.
«
When not using PZ-60DR-E, the function
selection switch for “Power supply/exhaust
when operation starts” (SW2-3) on the
Lossnay circuit board is set to ON.
«
When using PZ-60DR-E, the supply fan speed
setting and the exhaust fan speed setting are
set to “L” with the function selection of the
remote controller.
«
When not using PZ-60DR-E, the function selection
switches for “Supply fan fixed at Low speed”, and
“Exhaust fan fixed at Low speed” (SW2-4, SW2-5)
on the Lossnay circuit board are set to ON.
«
In a mixture of the LGH-15 to 100 types and the
LGH-150 and 200 types, the 150 and 200 types
are set to “Main”. (Extra Low fan speed operation
is not available.)
«
Check the High/Low/Extra Low
fan speed switching input (CN16).
(Refer to page C-70 and C-73)
«
Check the setting of “power sup-
ply/exhaust when operation
starts” with the PZ-60DR-E func-
tion selection. (Refer to page C-90)
«
Check the function selection
switch (SW2-3).
(Refer to page C-73)
«
Check the supply fan speed set-
ting and the exhaust fan speed
setting with the PZ-60DR-E func-
tion selection. (Refer to page C-90)
«
Check the function selection
switches (SW2-4, SW2-5).
(Refer to page C-73)
«
Set the LGH-15 to 100 types to
“Main” and the LGH-150 and
200 types to “Sub”.
(Refer to page C-69)
Error
Cause
Action
5
Cannot stop the Lossnay
with PZ-60DR-E. (“24HR
VENTILATION” is displayed).
«
24-hour ventilation is set to “on” with the PZ-
60DR-E function selection.
«
Check the 24-hour ventilation
setting with the PZ-60DR-E func-
tion selection. (Refer to page C-89)
10.2.3 Troubleshooting 3 : The remote controller operation is disabled or irregular
1 2
Содержание LGH-100RX5 -E
Страница 1: ...Lossnay Remote Controller ...
Страница 2: ......
Страница 94: ...C 94 ...
Страница 95: ...C 95 5 ...
Страница 96: ...C 96 ...
Страница 97: ...C 97 ...
Страница 98: ...C 98 5 3 ...
Страница 99: ...C 99 ...
Страница 106: ...Y08 004 Jan 2009 MEE ...