6 INSTALLATION AND WIRING
6.4 Wiring of Terminal Block for Module Power Supply and FG
Precautions
• Use a bar solderless terminal for the wiring to the push-in type spring clamp terminal block. If a stripped wire is inserted into
a wire insertion opening, the wire cannot be securely clamped.
• For how long the wire should be stripped, follow the specifications of the bar solderless terminal used. To attach a bar
solderless terminal to a wire, use a crimping tool.
• Before inserting a bar solderless terminal into a wire insertion opening (1), check the shape of the opening and the shape of
the terminal. Insert the terminal paying attention to the orientation. If a bar solderless terminal larger than wire insertion
opening (1) is inserted, the terminal block may be damaged.
Do not install the FG lines and communication cables together or closely each other. Doing so may result in
malfunction due to noise.
Processing method of the cable terminal
Strip the cable about 10mm from the tip to connect a bar solderless terminal at the stripped area. Stripping the cable too long
may cause electric shock or short circuit between adjacent terminals because the conductive part sticks out of the terminal
block. Stripping the cable too short may cause a poor contact to the spring clamp terminal part.
2.8mm
2.0mm
(1)
Cable
Around 10mm