APPX
Appendix 5 EMC and Low Voltage Directives
155
A
Measures to comply with the Machinery Directive
The Machinery Directive (2006/42/EC) requires that machinery satisfy the three pillars of safety: mechanical safety, electrical
safety, and worker safety.
This product complies with the Machinery Directive (2006/42/EC). Before using this product, please read this manual, the
relevant manuals, the manuals for standard programmable controller, and the safety standards carefully and pay full attention
to safety to handle the product correctly.
The descriptions are based on the requirements of the Machinery Directive and the harmonized standards. However, they do
not guarantee that the entire machinery constructed according to the descriptions complies with the Machinery Directive. The
manufacturer of the machinery must determine the testing method for compliance and declare conformity to the Machinery
Directive.
*1 The module is an open type device (a device designed to be housed in other equipment) and must be installed inside a conductive
control panel. The tests were conducted with the module installed in a control panel.
Specifications
Test item
Test description
Value of standard
IEC 61000-6-7: 2015
EN 61000-4-2
EN 61000-6-7
Electrostatic discharge
immunity
Static electricity is applied to the
cabinet of the equipment.
8kV contact discharge
EN 61000-4-3
EN 61000-6-7
Radiated, radio-
frequency
electromagnetic field
immunity
Electric fields are radiated to the
product.
80% AM modulation@1kHz
• 80 to 1000MHz: 20V/m
• 1.4 to 2.0GHz: 10V/m
• 2.0 to 6.0GHz: 3V/m
• 84.000, 137 to 174, 219.500, 380 to 400, 420 to 470, 698 to
960MHz: 20V/m
• 1.24 to 1.30, 1.428 to 2.0GHz: 10V/m
• 2.0 to 2.7, 3.3 to 3.6, 5.15 to 5.925GHz: 3Vm
EN 61000-4-4
Fast transient burst
immunity
Burst noise is applied to the power
lines and signal lines.
• AC main power: 4kV
• DC main power, DC I/O, I/O, communication: 2kV
EN 61000-4-5
EN 61000-6-7
Surge immunity
A lightning surge is applied to the
power lines and signal lines.
• AC main power, AC/DC main power: 4kV
• DC I/O, I/O, communication: 2kV
EN 61000-4-6
EN 61000-6-7
Conducted RF
immunity
High frequency noise is applied to
the power lines and signal lines.
80% AM modulation @1kHz,
• 0.15 to 80MHz: 20V
• 3.39, 6.780, 13.560, 27.120, 40.680MHz: 20V
EN 61000-4-11
Voltage dips and
interruption immunity
A momentary power failure is
caused to the power supply voltage.
• Apply at 0%, 1 cycle, and zero-cross point
• 0%, 250/300 cycles (50/60Hz)
• 40%, 10/12 cycles (50/60Hz)
• 70%, 25/30 cycles (50/60Hz)
EN 61000-6-7
EN 61000-4-6-16
Conducted common-
mode voltage immunity
Common-mode noise is applied to
the power lines and signal lines.
• 1.5 to 15kHz: 1 to 10V
• 15 to 150kHZ: 10V
• 16.7, 50, 60, 150, 180Hz: 10V (continuously)
• 16.7, 50, 60Hz: For short period of time (1s)