20
3 SPECIFICATIONS
3.2 Performance Specifications
*1 The performance specifications vary depending on firmware versions of modules used. (
Page 159 Added and Changed Functions)
*2 To connect to the safety remote I/O module, use the power supply that meets the following conditions:
SELV (Safety Extra Low Voltage): Product with reinforced insulation from the hazardous potential part (60V or higher)
LVD applicable product
Output voltage specifications: 20.4 to 28.8VDC (ripple ratio: 5% or less)
*3 Only one wire can be inserted into a wire insertion opening. Multiple wires cannot be connected to a terminal. Connecting two or more
wires may cause a poor contact.
*4 To connect to the safety remote I/O module, use a power supply whose output hold time is 10ms or longer.
■
External wiring
Weight
0.25kg
(1) The COM+ terminals can supply 24VDC as well.
Item
NZ2GNSS2-8D
18
4
3
2
1
22
28
21
27
19
39
20
38
40
31
IO24V
IO24V
IO24G
IO24G
GND
T1
T1
+24V
24V IN
0V IN
T0
T0
X0
X1
X2
X3
11
NC
NC
COM-
COM-
1
2
3
1
2
3
+24V
24G
FG
8
10
29
9
30
X7
COM+
COM+
COM-
COM-
+24V
(1)
Internal
circuit
I/O terminal block
Terminal block for module
power supply and FG
24VDC
24VDC
Reverse
connection
protection circuit
A device such
as safety sensor
Control
output 1
Control
output 2
24VDC
Pin No.
Signal name
Safety switch
Fuse
Содержание CC-Link IE-NZ2GNSS2-16DTE