146
APPX
Appendix 4 Remote Buffer Memory
■
Input dark test execution setting
Set whether to perform the input dark test function of the diagnostic function in the safety remote I/O module in units of 1
point.
When "Wiring selection of input" is set to "0: Not used" or "3: General single", this parameter is ignored.
■
Input dark test pulse OFF time setting
Set the width of the OFF pulses that the terminals T0 and T1 output, on a module-by-module basis.
When "Wiring selection of input" is set to "0: Not used" or "3: General single", or when "Input dark test
execution setting" is set to "1: Do not perform", this parameter is ignored.
■
Number of pulse output for input dark test
Set the number of pulse output for input dark test on a module-by-module basis.
When "Wiring selection of input" is set to "0: Not used" or "3: General single", or when "Input dark test
execution setting" is set to "1: Do not perform", this parameter is ignored.
Module
Address (hexadecimal)
Name
Setting range
Default value
Input module
0160H to 0167H
Input dark test execution setting X0 to X7
0: Perform
1: Do not perform
0: Perform
Output module
I/O combined module
0160H to 0167H
Module
Address (hexadecimal)
Name
Setting range
Default value
Input module
0170H
Input dark test pulse OFF time
0: 400
s
1: 1ms
2: 2ms
0: 400
s
Output module
I/O combined module
0170H
Module
Address (hexadecimal)
Name
Setting range
Default value
Input module
0171H
Number of pulse output for input dark
test
0: 1 time
1: 2 times
2: 3 times
0: 1 time
Output module
I/O combined module
0171H