58
7 SETTINGS
7.2 Parameter Setting
Basic module
parameter
Double input discrepancy auto recovery
setting
When double input discrepancy
occurs, set whether to keep the
abnormal point in the stop state,
or to automatically return when
the error is resolved.
0: Not used
1: Used
Page 145 Double input
discrepancy auto
recovery setting
Input dark test pulse OFF time setting
Set the width of the OFF pulses
that the terminals T0 and T1
output, on a module-by-module
basis.
0: 400
s
1: 1ms
2: 2ms
Page 146 Input dark test
pulse OFF time setting
Number of pulse output for input dark test
Set the number of OFF pulses for
input dark test diagnostic on a
module-by-module basis.
0: 1 time
1: 2 times
2: 3 times
Page 146 Number of
pulse output for input
dark test
Fast logic pattern setting
Set the logic patterns for the fast
logic function.
0: Not used
1: Pattern 1
2: Pattern 2
3: Pattern 3
4: Pattern 4
Page 148 Fast logic
pattern setting
Fast logic interlock mode setting
When the fast logic function is
enabled, set whether to perform
output point interlock when the
output is turned off.
0: Enable
1: Disable
Page 148 Fast logic
interlock mode setting
Basic module
parameter (X0 to
X7)
Wiring selection of inputs X0 to X7
Set the input wiring method.
0: Not used
1: Safety double wiring
(NC/NC)
2: Safety single
3: General single
Page 144 Wiring
selection of input
Input response time X0 to X7
To prevent malfunction of the
input signal, set the sensitivity to
react to the input signal in units of
1 point.
0: 1.0ms
1: 1.5ms
2: 5ms
3: 10ms
4: 20ms
5: 50ms
6: 70ms
Double input discrepancy detection setting
(X0, X1) to (X6, X7)
Set whether to detect double input
discrepancy in units of 2 points.
0: Detect
1: Do not detect
Page 145 Double input
discrepancy detection
setting
Double input discrepancy detection time (X0,
X1) to (X6, X7)
Set the double input discrepancy
allowed time in units of 2 points.
1 to 6000(
10ms)
Page 145 Double input
discrepancy detection
time
Input dark test execution setting X0 to X7
Set whether to perform the input
dark test function of the diagnostic
function in the safety remote I/O
module in units of 1 point.
0: Perform
1: Do not perform
Page 146 Input dark test
execution setting
Basic module
parameter (Y0 to
Y7)
Wiring selection of output Y0 to Y7
Set the wiring selection of output
in units of 1 point.
0: Not used
1: Safety double wiring
(Source/Source)
2: Safety single
Page 147 Wiring
selection of output
Output dark test execution setting Y0 to Y7
Set whether to perform the output
dark test function of the diagnostic
function in the safety remote I/O
module in units of 1 point.
0: Perform
1: Do not perform
Page 147 Output dark
test execution setting
Output dark test pulse OFF time setting Y0 to
Y7
Set the width of OFF pulses used
for an output dark test in units of 1
point.
0: 400
s
1: 1ms
2: 2ms
Page 148 Output dark
test pulse OFF time
setting
Number of pulse output for output dark test
Y0 to Y7
Set the number of OFF pulses for
output dark test diagnostic in units
of 1 point.
0: 1 time
1: 2 times
2: 3 times
Page 148 Number of
pulse output for output
dark test
Item
Setting details
Setting range
Reference
Содержание CC-Link IE-NZ2GNSS2-16DTE