7 SETTINGS
7.2 Parameter Setting
Parameter processing of slave station
The following describes the procedure for setting module parameters of the safety remote I/O module from the "Network
Configuration Settings" window.
Parameter setting
Operating procedure
1.
Open the "CC-Link IE TSN Configuration" window.
[Navigation window]
[Parameter]
[Module Information]
Model
[Basic Settings]
[Network Configuration
Settings]
2.
Select the safety remote I/O module in "Module List" and drag and drop it to the list of stations (1) or the network map (2).
"Station Type", "RX/RY Setting", and "RWw/RWr Setting" are automatically input. Change a value as necessary.
3.
Right-click the safety remote I/O module and select "Parameter of Slave Station" to display the "Parameter of Slave
Station" window.
(1)
(2)
Содержание CC-Link IE-NZ2GNSS2-16DTE