3 SPECIFICATIONS
3.2 Performance Specifications
*1 The performance specifications vary depending on firmware versions of modules used. (
Page 159 Added and Changed Functions)
*2 To connect to the safety remote I/O module, use the power supply that meets the following conditions:
SELV (Safety Extra Low Voltage): Product with reinforced insulation from the hazardous potential part (60V or higher)
LVD applicable product
Output voltage specifications: 20.4 to 28.8VDC (ripple ratio: 5% or less)
*3 Only one wire can be inserted into a wire insertion opening. Multiple wires cannot be connected to a terminal. Connecting two or more
wires may cause a poor contact.
*4 To connect to the safety remote I/O module, use a power supply whose output hold time is 10ms or longer.
Applicable solderless
terminal
Terminal block for module
power supply and FG
Page 44 Applicable solderless terminal
I/O terminal block
Page 49 Applicable solderless terminal
Multicast filter
Available
Cyclic transmission
RX/RY points
16 points
RWr/RWw points
4 points
SA\X / SA\Y points
SA\X: 32 points, SA\Y: 16 points
Module power supply
Voltage
24VDC (ripple ratio: 5% or less) (allowable voltage range: 20.4 to 28.8VDC)
Current
170mA
Protection function
Module power supply overvoltage protection function, module power supply overcurrent protection
function
Fuse
1.6A (user-unchangeable)
Safety element
Type B, HFT = 1, SC 3
Weight
0.25kg
Item
NZ2GNSS2-16DTE