110
10 TROUBLESHOOTING
10.3 Unit Test
10.3
Unit Test
Run a unit test to check if there is any hardware failure in the safety remote I/O module.
1.
Power off the power supply of the safety remote I/O module.
2.
Connect P1 and P2 of the safety remote I/O module with an Ethernet cable.
3.
Set the IP address setting switch as follows.
• IP address setting switch (x1): F
• IP address setting switch (x16): F
4.
Power on the power supply of the safety remote I/O module.
5.
Unit test begins.
The RUN LED flashes during the unit test.
6.
The RUN LED turns on when the unit test is completed.
• If the test is completed normally, the ERR. LED does not turn on, but remains off.
• If the test is completed with an error, the ERR. LED turns on. If the test is completed with an error, replace the Ethernet
cable and run the test again. If the test fails again, it may be due to a hardware failure in the safety remote I/O module.
Please consult your local Mitsubishi representative.
Precautions
If the safety remote I/O module is connected to the network while IP address setting switch (x16) and IP address setting
switch (x1) are set to F, data link may not be properly performed on safety remote I/O modules of other stations.
Set appropriate values both for IP address setting switch (x16) and IP address setting switch (x1), and connect the safety
remote I/O module to the network.