84
8 FUNCTIONS
8.4 Safety Output
■
When fast logic interlock is disabled
Even when the output is turned off by the fast logic function, fast logic READY (SA\XC) remains on and the fast logic function
does not stop. Operations of the fast logic initial request flag (SA\Y8) and fast logic start flag (SA\Y9), or operations of the
reset signal X7 and start signal X6 will be ignored.
Since fast logic interlock is disabled, output resumes when an input signal that satisfies the logic pattern conditions is turned
on again.
The operation when the fast logic pattern setting is Pattern 2 is shown below.
Executed by the program
(1) Even if the fast logic initial request flag (SA\Y8) is turned off and on, the fast logic initial completion flag (SA\XD) does not change.
(2) Even if the fast logic start flag (SA\Y9) is turned off and on, the fast logic initial completion flag (SA\XD) does not change.
ON
ON
ON
ON
(1)
(2)
OFF
OFF
OFF
ON
ON
OFF
OFF
ON
ON
Fast logic READY (SA\XC)
Fast logic initial request flag
(SA\Y8), Reset signal (X7)
Fast logic start flag (SA\Y9),
Start signal (X6)
Fast logic initial completed flag
(SA\XD)
Safety output enable signal
(SA\Y0, SA\Y1)
Module operation mode
Safety operation mode
Input signal (X0, X1)
Input signal (X4, X5)
Output signal (Y0, Y1)
Input signal (X2, X3)