8 FUNCTIONS
8.4 Safety Output
87
8
Fast logic function parameter setting method
■
Fast logic pattern setting
Enable/disable the fast logic function and set the logic pattern.
Fast logic pattern setting is done with "Fast logic pattern setting" from the "Parameter of Slave Station" window of the
engineering tool.
For details on the logic patterns, refer to the following.
Page 79 Logic patterns of fast logic function
Precautions
When "Fast logic pattern setting" is other than "0: Not used", the parameter settings of "Wiring selection of input" and "Wiring
selection of output" in the safety remote I/O module are automatically replaced with the following setting values. The replaced
setting values cannot be checked on the "Parameter of Slave Station" window.
Item
Setting range
Fast logic pattern setting
0: Not used
1: Pattern 1
2: Pattern 2
3: Pattern 3
4: Pattern 4
No.
Fast logic pattern setting
Wiring selection of input/output
Setting value
1
Pattern 1
Four safety double wiring inputs (without reset
signal)
Wiring selection of input
X0
Safety double wiring (NC/NC)
X1
X2
Safety double wiring (NC/NC)
X3
X4
Safety double wiring (NC/NC)
X5
X6
Safety double wiring (NC/NC)
X7
Wiring selection of output
Y0
Safety double wiring (Source/Source)
Y1
Y2
Not used
Y3
Y4
Y5
Y6
Y7
2
Pattern 2
Three safety double wiring inputs (with reset
signal)
Wiring selection of input
X0
Safety double wiring (NC/NC)
X1
X2
Safety double wiring (NC/NC)
X3
X4
Safety double wiring (NC/NC)
X5
X6
Safety single
X7
Safety single
Wiring selection of output
Y0
Safety double wiring (Source/Source)
Y1
Y2
Not used
Y3
Y4
Y5
Y6
Y7