8 FUNCTIONS
8.4 Safety Output
77
8
Setting method
Set the safety output wiring selection in "Wiring selection of output" from the "Parameter of Slave Station" window of the
engineering tool.
Set safety output to either "1: Safety double wiring (Source/Source)" or "2: Safety single".
• When "Wiring selection of output" Yn is set to "0: Not used", output data is always off.
• When "Wiring selection of output" Yn (n: even number) is set to "1: Safety double wiring (Source/Source)",
set Yn+1, the partner of Yn, to "1: Safety double wiring (Source/Source)".
• When "Wiring selection of output" Yn (n: even number) is set to other than "1: Safety double wiring (Source/
Source)", do not set Yn+1, the partner of Yn, to "1: Safety double wiring (Source/Source)".
Item
Setting range
Wiring selection of output Yn
0: Not used
1: Safety double wiring (Source/Source)
2: Safety single