4.4.2.14 Diagnosis
The diagnosis function outputs the status of the controller in "plain text" and is used to quickly read
out the current status.
Communication
object 26 "Diagnosis - Status"
is used for the output. This is permanently
displayed and sends automatically with every change.
The following messages can be sent out by the diagnosis function:
Byte 0-1
Byte 3
Byte 5-11
Byte 13
Info
Heating/Cooling Operation mode
Control value > 0%, if
„yes“: Value 1
Possible
messages
Heating: H
Comfort
Control value = 0%: 0
Cooling: C
Standby
Control value > 0%: 1
Night
Frost
Heat
ComProl
–
Comfort
prolongation
active
Window -
Window contact
active
BIT
–
Channel
operating mode
switching 1 Bit
PWM BYTE
–
Channel
operating mode
continuous 1 Byte
Special messages
Locked
Channel is locked
Contr Flowtemp
Control value reduced by flow temperature
Contr Dewpoint
Control value reduced by dew point
Setpoint Guide
Control value reduced by outdoor temperature/reference
variable
Dew point alarm The dew point alarm is active
Table 56: Overview
–
Diagnosis text