Technical Manual
Glass Room Temperature Controller Smart SCN-RTRGx.02
MDT technologies GmbH •
51766 Engelskirchen • Papiermühle 1
•
Germany
Phone: +49-2263-
880 • [email protected] • www.mdt.de
94
94
4.5.3.10 Basic function
–
Send value
Single-button function
Important:
Basic functions for the single-button function are available for selection if the
function of buttons 1 or 2 is set to "external function"!
The following figure shows the available settings:
Figure 52: Settings
–
Send value
The following table shows the available settings:
ETS-Text
Dynamic range
[Default value]
Comment
Datapoint type
▪
1Byte DPT 5.005 Decimal factor
(0…255)
▪
1Byte DPT 5.001 Percent value
(0…100%)
▪
1Byte DPT 17.001 Scene number
Setting the datapoint type for the
value to be sent.
Table 102: Settings
–
Send value
Each time the button is pressed, the set value is always sent.
The adjustable value ranges are 0 - 100% (percentage value), 0 - 255 (value) or 1 - 64 (scene).
The following table shows the available communication objects:
Number Name/Function
Length Usage
62
Button 1
–
send value, send percent value,
send scene
1 Byte Sending the value.
DPT depending on the parameter setting
65
Button 1
–
Status for display
1 Byte Receiving the status.
DPT depending on parameter setting.
Not available for scene number.
Table 103: Communication objects
–
Send value
For a description of "Representation on the display", " Button/Object description" and " Lock
object", see chapter